ADEMCO VISTA-15P Manual Pemrograman - Halaman 3

Jelajahi secara online atau unduh pdf Manual Pemrograman untuk Sistem Keamanan ADEMCO VISTA-15P. ADEMCO VISTA-15P 17 halaman. Programming auto arming and disarming schedules
Juga untuk ADEMCO VISTA-15P: Panduan Instalasi Cepat (2 halaman), Manual Pemrograman (17 halaman), Panduan Pengguna (20 halaman), Panduan Instalasi Cepat (2 halaman), Panduan Instalasi Cepat (2 halaman), Manual Pemrograman (2 halaman), Panduan Cepat (2 halaman)

ADEMCO VISTA-15P Manual Pemrograman
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Entries shown in dashed boxes indicate partition entries for VISTA-20P only (not applicable for VISTA-15P).
Field
Function
SYSTEM SETUP ( ✱ 20– ✱ 29)
∗ 20
INSTALLER CODE
✱ 21
QUICK ARM ENABLE
✱ 22
RF JAM OPTION
✱ 23
FORCED BYPASS
∗ 24
RF HOUSE ID CODE
✱ 26
CHIME BY ZONE
✱ 27
X–10 HOUSE CODE
✱ 28
ACCESS CODE FOR
4285/4286 PHONE MODULE
✱ 29 LONG RANGE RADIO OUTPUT
ZONE SOUNDS AND TIMING ( ✱ 31 – ✱ 39)
✱ 31
ONE AUDIBLE ALARM PER ZONE
✱ 32
FIRE ALARM SOUNDER TIMEOUT
✱ 33
ALARM SOUNDER TIMEOUT
✱ 34
EXIT DELAY
✱ 35
ENTRY DELAY #1 (zone type 01)
✱ 36
ENTRY DELAY #2 (zone type 02)
∗37
AUDIBLE EXIT WARNING
✱ 38
CONFIRMATION OF ARMING DING
✱ 39
POWER UP IN PREVIOUS STATE
DIALER PROGRAMMING ( ✱ 40 – ✱ 42)
Enter the number of digits shown. Do not fill unused spaces. Enter 0–9; #+11 for ' ✱ '; #+12 for '#'; #+13 for a 2-second pause. If fewer than the
maximum digits entered, exit the field by pressing [✶] and next desired field number.
∗40
PABX ACCESS CODE
∗41
PRIMARY PHONE No.
∗42
SECOND PHONE No.
352*5$00,1*)250
Data Entries
|
|
Part. 1 Part.2
[0]
Part. 1 Part. 2
|
Part. 1 Part. 2 Common
[0]
[0]
|
[00]
(Partition 1 only)
[0]
[0]
[0]
[1]
|
Part. 1 Part. 2
|
Part. 1 Part. 2
|
Part. 1 Part. 2
Part. 1 Part. 2
Part. 1 Part. 2
[1]
|
|
Enter up to 6 digits. To clear entries from field, press ✱40✱ .
|
|
|
|
|
|
|
Enter up to 20 digits. To clear entries, press ✱ 41 ✱ .
|
|
|
|
|
|
|
Enter up to 20 digits. To clear entries, press ✱ 42 ✱ .
Programmable Values
4 digits, 0–9
|
[4112]
0 = no; 1 = yes
[0,0]
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
0 = none UL: must be "0"
[0,0]
1 = bypass open zones
00 = disable all wireless keypad usage
|
|
01–31 = using 5827, 5827BD or 5804BD keypad
[00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3,
using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
for " ✱ ", or # + 12 for "#".
UL: must be "00" for UL Commercial Burg. installations
0 = disable; 1 = enable
0 = no UL: must be "0"; 1 = yes
0 = sounder stops at timeout;
1 = no sounder timeout UL: must be "1" for fire install.
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min;
4 = 16 min; UL: minimum "1" (4 min.)
00–99 = seconds of exit delay time for each partition
|
[70,70]
Common zones use same delay as partition 1.
00–99 = seconds of entry delay #1 time for each
|
[30,30]
partition; UL: 45 seconds max.
Common zones use same delay as partition 1.
00–99 = entry delay #2 time for each partition;
|
[60,60]
UL: 60 seconds max.
Common zones use same delay as partition 1.
0 = no; 1 = yes
[1,1]
0 = no; 1 = yes (wired keypads and RF)
[0,0]
2 = yes, RF only
0 = no; 1 = yes UL: must be "1"
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
– 3 –
|
|
|
|
|
|
|
|