DynaGen GSC400 Series Panduan Pemrogram - Halaman 3
Jelajahi secara online atau unduh pdf Panduan Pemrogram untuk Pengontrol DynaGen GSC400 Series. DynaGen GSC400 Series 4 halaman. For generator
Juga untuk DynaGen GSC400 Series: Panduan Utilitas Kalibrasi (18 halaman)
Installing the USB Serial Port Driver
(Vista, Windows XP, 2000).
To use a USB cable to connect to the GSC400 programmer you must install the USB serial
driver. This will allow you to communicate over USB by selecting a serial port. If you are using
a serial cable you can skip this section.
1. If the GSC400 programmer is connected to the computer disconnect the programmer
from the computer.
2. On the installation CD go to the "USB Drivers/Vista, XP, 2000, Server 2003"
3. Double click on "CDM_Setup.exe".
4. The program will extract the drivers.
5. Connect the USB cable. Windows will find the hardware and install the drivers
automatically. The default comm. port for USB is usually com5. To change or confirm
this, see below.
(Vista x64, Windows XP Professional x64, Windows Server 2003 x64)
1. If the GSC400 programmer is connected to the computer disconnect the programmer
from the computer.
2. On the installation CD go to the "USB Drivers/ x64 - Vista, XP, Server 2003"
3. Double click on "CDM_x64_Setup.exe".
4. The program will extract the drivers.
5. Connect the USB cable. Windows will find the hardware and install the drivers
automatically. The default comm. port for USB is usually com5. To change or confirm
this, see below.
(Windows 98, Windows ME)
1. If the GSC400 programmer is connected to the computer disconnect the programmer
from the computer.
2. On the installation CD go to the "USB Drivers/ Win98, Win ME"
3. In the same folder open "Windows_98_Installation_Guide.pdf". Go to page 8 and follow
the instructions under "Installing VCP Drivers" with the following exceptions: The
unzipped drivers are located in the "USB Drivers/ Win98, Win ME R10906" folder. You
do not need to download them.
Uninstalling the USB Serial Port Driver (Vista, Windows XP, 2000, 98, ME)
1. (For Win. XP only): A recent security update from Microsoft has prevented the FTDI
Uninstaller from running. Go to "C:// Windows/System32". Right click on
"ftdiunin.exe" and click on the "Capability" tab. Check "Run this program in
compatibility mode for" and select Windows 2000.
GSC400 Programmer Manual
Revision 1.0 (22/12/2006)
3