Current - Phase B Delta Slope Calibration: 0
Current - Phase A Slope Calibration: -126
Current - Phase A Delta Slope Calibration: -3960
--------------------------------
Click Next to continue.
Current for phase A, B, and C are: 0.1A, 0A, and 0A.
Reading current ...
Click next.
Set the load to the high point and enter the curent read in the box above.
----------------------------
Click Next to continue.
Current for phase A, B, and C are: 0.1A, 0A, and 0A.
Reading current ...
Click next.
Set the load to the low point and enter the value read in the box above.
----------------------------
Press next to continue.
Voltage for phase A, B, and C are: 116.2V, 116V, and 115.7V.
Reading system voltage...
Start the Engine/Generator and click OK once the Generator is running.
Current CT ratio: 100A:5A
Getting CT Ratio.
Make note of these in case you need to revert back.
Current slopes for phases A, B, and C are: -126, 55, -29.
Current offsets for phases A, B, and C are: 0, 0, 0.
Voltage slopes for phases A, B, and C are: 18, 18, 25.
Voltage offsets for phases A, B, and C are: 0, 0, 0.
Getting calibration coefficients..
Place the controller in the Off Mode. Click OK once in the Off Mode.
Click the Next button to continue once the voltages are entered.
Enter the voltages for Phase A, B, and C in the boxes above.