2.0 CALCULATED FLOW SET UP
2.1 SETTING MEASURED SUPPLY AIR FLOW
The measured flow is the amount of air that enters the
return side of the air handler from the outside air vent.
Enter the measured flow. To accommodate variable speed
air handlers, you can enter different values for heat, cool
and fan. Factory default is 90 CFM.
Press MODE to advance to the next setting.
2.2 SETTING CODE REQUIRED CONSTANT AIR FLOW
Set the required continuous air flow in CFM based on relevant codes. For ASHRAE 62.2
see Appendix A. Factory default is 30 CFM. The AirCycler® g1 will calculate run times
based on settings 2.1 and 2.2.
Press MODE to advance to the next setting
2.3 SETTING OPTIONAL MIXING TIME
If the user needs more central fan time for whole house mixing than the amount that
is provided by ventilation time, the central fan can be configured to run an additional
time period to complete the mixing period. Factory default is 0 or OFF. To use/change
this setting press UP arrow. The fresh air damper will not be open during this extra time.
Press MODE to advance to next setting.
2.4 SETTING OPERATION HOURS
If the user does not want the ventilation system to run throughout the day you can set
ON time and OFF time. Factory default is NO. If you are not setting an ON and OFF time,
press MODE and continue to section 2.5.
If you want to set hours of operation press the UP arrow for yes [YS]. Press MODE to select
yes. The AirCycler® g1 will prompt you to enter the hour you would like the ventilation
to begin and the hour you want it to end followed by the current time.
Set the hour you want ventilation to START. Press MODE to advance to the next setting.
Set the hour you want the ventilation to STOP. Press MODE to advance to next setting.
2.4.1 SETTING CURRENT TIME
Enter the current time. Press MODE to save all settings. Setup is complete.
2.5 CALCULATED FLOW SETUP IS COMPLETE
Set up is complete. The AirCycler® g1 will now return to normal operation.