Automation Direct ProSense VFS75-26-1001 Panduan Petunjuk Pengoperasian - Halaman 11

Jelajahi secara online atau unduh pdf Panduan Petunjuk Pengoperasian untuk Alat Ukur Automation Direct ProSense VFS75-26-1001. Automation Direct ProSense VFS75-26-1001 18 halaman. Vortex flow meter

8.1.1 Explanation main menu

Switching output with hysteresis function
SP1
Set point 1 = upper limit value at which OUT1 switches.
rP1
Reset point 1 = lower limit value at which OUT1 switches off.
SP2
Set point 2 = upper limit value at which OUT2 switches.
rP2
Reset point 2 = lower limit value at which OUT2 switches off.
Switching output with window function
FH1
Set point 1 = upper limit value at which OUT1 switches.
FL1
Reset point 1 = lower limit value at which OUT1 switches.
FH2
Set point 2 = upper limit value at which OUT2 switches.
FL2
Reset point 2 = lower limit value at which OUT2 switches.
Frequency output
FEP1
Process value end point on OUT1.
FrP1
Frequency at process value end point (FEP1) on OUT1.
FSP2
Process value start point on OUT2 (only if SEL2 = TEMP).
FEP2
Process value end point on OUT2.
FrP2
Frequency at process value end point (FEP2) on OUT2.
Extended functions
EF
Opening of the lower menu level.
11