DALI Auxiliary Input Interface
Installation Manual
WARNING:
Do not connect DALI or Dry contact
wires to mains. Dry contact & DALI wires are NOT
SELV and should never be considered touch safe.
Functional level of isolation or better is required
between DALI / dry contact wires and mains cabling.
features
4 x Dry Contact Inputs – Presented on a 2.5mm pitch
165mm long fly leads.
Powered from the DALI Network – No need for an external
power supply.
DALI network – Different DALI network devices can be
connected in any order along the network. The DPMI940-
DALI does not need to be directly connected to the lighting
groups that is controlling
Simple Installation - Compact enclosure allows the device to
be conveniently placed near the device to be controlled. All
connections are accessible without disassembly
Connecting volt free inputs
diagram
Flying Lead inputs
wire
Function
1
COM
2
DC1
3
DC2
4
DC3
5
DC4
DA
6
DA
7
important notes
Read Instructions – We recommend that you read this
Instruction Manual prior to commencement of installation.
Special Programming – This device will only operate in basic
modes unless programmed via a computer.
commissioned using Envision software.
DALI bus ready – This device can only be used in junction with a
Philips Dynalite multi master controller such as the DDBC120-
DALI. DALI is a non polarised communication protocol.
Installation Location – Install in a dry location, close to the
equipment to be interfaced with.
Dry contact wires: Maximum recommended length of dry
connector wires is 1 meter. Wires should be kept away from any
mains cables. Inputs must not be connected to any voltage
source, only voltage free dry contacts should be used
Colour
Purple
GREY
GREY
GREY
GREY
ORANGE
ORANGE
Electrical diagram
Device is to be