AutomationDirect IronHorse GSDA-DP-S Panduan Pengguna - Halaman 11
Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Konverter Media AutomationDirect IronHorse GSDA-DP-S. AutomationDirect IronHorse GSDA-DP-S 16 halaman. Signal conditioner/generator
S
P
oftWAre
ArAMeterS
Parameter
Select parameter 0 to return to Run
0
mode
1
Model Number
2
Software Build
3
Hardware Version
4
Serial Number - Major (Reserved)
5
Serial Number - Minor (Reserved)
10
Generate/Scale
11
Display Intensity
12
Display Zero Blanking
13
Decimal Point Position
15
Keypad Mode
16
Keypad Scroll Delay
18
Power-Up Mode
19
Power-Up Value
20
Display Value at Minimum Output
21
Display Value at Maximum Output
25
Output % - Minimum
26
Output % - Maximum
30
IN1 Input Configuration
31
IN1 Setpoint
35
IN2 Input Configuration
36
IN2 Setpoint
95
Restore Settings to Factory Default
IronHorse GSDA-DP-S User Manual – 1st Edition – 09/18/2019
Description
n/a
Read-Only Parameters
90 – GSDA-DP-S
1–9999
1–9999
n/a
n/a
General Setup Parameters
1–Generate
2–Scale
0–31 (Dim–Bright)
1–___X Show at least 1 digit
2–__XX Show at least 2 digits
3–_XXX Show at least 3 digits
4–XXXX Show at least 4 digits
0–Decimals Disabled (XXXX)
1–X�XXX
2–XX�XX
3–XXX�X
4–XXXX�
1–Linear, constant rate
2–Non-linear, accelerating rate
0–30 (Fast–Slow)
1–Default to Zero Display
2–Default to Power-up Value
3–Default to Previous Running
Value
0–9999
Display and Output Setup Parameters
-9999–9999
-9999–9999
0–1000
0–1000
Input #1 (IN1) Setup Parameters
1–Output 0% when IN1 Low
2–Output 0% when IN1 High
3–Output Setpoint when IN1 Low
4–Output Setpoint when IN1 High
5–Output 100% when IN1 Low
6–Output 100% when IN1 High
7–Lock Set Point when IN1 Low
-9999–9999
Input #2 (IN2) Setup Parameters
1–Output 0% when IN2 Low
2–Output 0% when IN2 High
3–Output Setpoint when IN2 Low
4–Output Setpoint when IN2 High
5–Output 100% when IN2 Low
6–Output 100% when IN2 High
7–Lock Set Point when IN2 High
-9999–9999
Parameter Memory Commands
0–Do Nothing and Exit
5–Restore Factory Defaults
Value Range
Units
(Eng�
Units)
(Eng�
Units)
(Eng�
Units)
1/10 %
1/10 %
(Eng�
Units)
(Eng�
Units)
Default
–
n/a
90
n/a
n/a
n/a
n/a
1
26
2
3
2
10
3
0
0
1000
0
1000
1
0
1
0
0
Page 11