ADEMCO 4192CPM Petunjuk Pemasangan dan Pemeliharaan

Jelajahi secara online atau unduh pdf Petunjuk Pemasangan dan Pemeliharaan untuk Alarm Asap ADEMCO 4192CPM. ADEMCO 4192CPM 4 halaman. Addressable ionization smoke detector

P-Mc,~
4192CPM Addressable
Ionization Smoke Detector
Installation and Maintenance
Instructions
Before instalkng detectors, please thoroughly
read the suppoting
Ademco control panel installation instructions,
which
provide detailed information on detector spacing, placement, zones, and special applications.
Copies of the installation
instructions
are available from Ademco. NFPA 72 and NEMA guidelines should also be observed.
=
Use this smoke detector only with panels that suppofl the detector's maintenance
feature:
ADEMCO VISTA 150, First Aleti FA1600C.
GENERAL
DESCRIPTION
The Model 4192CPM
dual-chamber
ionization
smoke detecto. uses a stat(>-of-the-art unipolar sensing chamber. This
detector is designed to provide open area protection and to be used with compatible
UL-hsted Ademco control panels.
An LED on each detector flashes every ten seconds. This LED can be Iatc!ted on by code command from ceflain con-
trol panels to indicate an alarm. [t can also be unlatched to the normal blinHng condition by the same control panels.
The 4192CPM
detector is intended for use in an Ademco 2-wire polling loop system. It uses two screw terminals for
connection
to the system. Both detector power and communication
betwe!en detector and control panel are accom-
plished over the same two wires.
SPECIFICATIONS
Base Diameter
5.0 inches (127 mm)
Cover Height
3.0 inches (76 mm)
Cover Diameter
3.15 inches (80 mm)
Loop Voltage Range:
7to 14VDC
Standby Current (max.):
1.56 mA (LED off); 3.56 mA (LED on)
Operating Temperature
Range:
5° to 131°F (-15° to 55°C)
NOTE
Do not install in locations where normal temperature
exceeds 120°F
(49"C)
Loop Unit Load:
2
MOUNTING
INSTRUCTIONS
Each 4192CPM
detector is supplied with a mounting
bracket tit that permits the detector to be mounted using several
techniques.
1. Units may be mounted directly to a 3-inch or 4-inch, 1-1/2-inch
deep octagonal
electrical
box using the supplied
mounting bracket (See Figures 1 and 2).
2. Units maybe
mounted to a 4-inch square electrical box by using a plast~?r ring with the supplied mounting bracket.
w
,,,fl~g$yziE;sT
o
~>y
",
.u...EmARRow,x\w,~
;" ~ ~
\
";:&$
..,-
Figure l.. Flush Mounting of Detector on Octagon
Box.
Hgure 2. Detector Mounting Bracket.
AD400-I 2-00
1
156-721-04
Ademco, 165 Hleen Way, Syosset, NY 11791
A7E2%3-02