Autometers Systems A-400P Brosur Pemrograman dan Instalasi - Halaman 13

Jelajahi secara online atau unduh pdf Brosur Pemrograman dan Instalasi untuk Alat Ukur Autometers Systems A-400P. Autometers Systems A-400P 17 halaman. Mid approved sgs.uk appendix b and d, measures kwh, kvarh, kvar,pf,hz, max demand, rs 485 modbus autometers v6 protocol, two pulse outputs, bi- directional measurement for import and export, back light lcd for full viewing angles, available as 1 phase 2 w

5.3.2 RS485/Mbus Output for Modbus RTU
*For A-400MT/-M
For Modbus RTU, the following RS485 communication parameters can be configured from the
set-up menu:
Baud rate 2400, 4800, 9600, 19200, 38400
Parity none / odd / even
Stop bits 1 or 2
RS485 network address nnn - 3-digit number, 001 to 247
*For A-400MB only
For Mbus, the following communication parameters
can be configured from the set-up menu:
Baud rate 300,600,2400, 4800, 9600
Parity none/ odd / even
Stop bits 1 or 2
Mbus network primary address nnn - 3-digit number,001 to 250 Mbus network secondary
address 00 00 00 00 to 99 99 99 99
Please contact us if your require the Modbus/Mbus protocol document.
5.4 Accuracy
Voltage .......................................
Current.......................................
Frequency..................................
Power factor..............................
Active power (W).......................
Reactive power (VAr)................
Apparent power (VA)................
Active energy (Wh)....................
Reactive energy (VARh)............
THD.............................................
Response time to step input...
5.5 Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy
is verified under nominal value (within the specified tolerance) of these conditions.
Ambient temperature.......................
Input waveform.................................
Input waveform.................................
5.6 Environment
Operating temperature............
Storage temperature................
Relative humidity.......................
Altitude.......................................
Warm up time............................
Vibration.....................................
Shock..........................................
* Maximum operating and storage temperatures are in the context of typical daily and
seasonal variation.
0.5% of range maximum
0.5% of nominal
0.2% of mid-frequncy
1% of unity (0.01)
±1% of range maximum
±1% of range maximum
±1% of range maximum
Class 1 IEC 62053-21 EN504 62053-21 70-3
±1% of range maximum
1% up to 31st harmonic
1s, typical, to >99% of final reading, at 50 Hz
23°C ± 2°C
50 Hz(MID)
50 or 60Hz ±2%(non-MID)
Sinusoidal (distortion factor < 0.005)
-25°C to +55°C*
-40°C to +70°C*
0 to 95%, non-condensing
Up to 3000m
1 minute
10Hz to 50Hz, IEC 60068-2-6, 2g
30g in 3 planes
www.autometers.co.uk
12