Autometers Systems A-45 Series Panduan Memulai Cepat
Jelajahi secara online atau unduh pdf Panduan Memulai Cepat untuk Alat Ukur Autometers Systems A-45 Series. Autometers Systems A-45 Series 2 halaman. Mid approved b and d
1. Introduction
This document provides operating, maintenance and installation instructions
of A-45 series. The unit measures and displays the characteristics of single
phase two wires application. It provides voltage, current, power, frequency,
power factor and energy information. A-45 series has both direct connect types
and 5A CT operated types. The direct connect type can work with direct load
45A. Two Pulse outputs and 1 remote communication port is provided.
This series covers 3 models:
Model
Current Input
A-45P
Direct connect 45A
A-45M
Direct connect 45A
A-45CTM
5A CT operated
2.Specifications
2.1 General Specifications
Voltage AC (Un).........................
230V
Voltage Range...........................
176~276V AC
Current Input............................
0.25~5(6)A
Power consumption.................
<2W/10VA
Frequency.................................
50/60Hz (50Hz only for MID version)
AC voltage withstand...............
4KV for 1 minute
Impulse voltage withstand......
6KV-1.2uS wavform
Overcurrent withstand............
20Imax for 0.01s
Pulse output rate......................
1000imp/kWh (default)
100/10/1 imp/kWh/kVarh (configurable)
Display........................................
LCD with white backlit
Max reading...............................
999999 kWh
2.2 Accuracy
Voltage...................................
0.5% of range maximum
Current..................................
0.5% of nominal
Frequency..............................
0.2% of mid-frequency
Power factor..........................
1% of Unity
Active power..........................
1% of range maximum
Reactive power......................
1% of range maximum
Apparent power....................
1% of range maximum
Active energy.........................
Class 1 IEC62053-21
.........................
Class B EN50470-3 (MID product only)
Reactive energy.....................
1% of range maximum
2.3 Environment
Operating temperature...............................
Storage and transportation temperature.
Reference temperature...............................
Relative humidity..........................................
Altitude..........................................................
Warm up time...............................................
Mechanical Environment.............................
Electromagnetic environment....................
Degree of pollution......................................
2.4 Mechanics
Din rail dimensions................
18x119x62 (WxHxD) DIN 43880 DIN rail
Mounting.................................
35mm
Sealing.....................................
IP51 (indoor)
Material...................................
self-extinguishing UL94V-0
3. Display
3.1 Initialization Display
When it is powered on, the meter will initialize and do self-checking.
Full Screen. It will last for 3 seconds
Software version. It will last for 3 seconds
1
Total active energy (kWh)
2
After the self-checking program, the meter display will show the total active
3
energy (kWh)
Product development is continuous and Autometers Systems Limited reserves the right to make alterations and manufacture without notice. Products as
delivered may therefor differ from the descriptions and illustrations in this publication
Autometers Systems Ltd. 4B Albany Road, Chorlton-cum-Hardy, Manchester M21 0AW
Email: [email protected] Phone: 00(44) 0161 861 9056 Fax: 0161 881 3745 www.autometers.co.uk
Communication
Pulse output only
Pulse plus Modbus
Pulse plus Modbus
-25°c to +55°c
-40°c to +70°c
23°c ±2°c
0 to 95%, non-condensing
up to 2000m
3s
M1
E2
2
A-45 SERIES
3.2 Scroll Display Button
After the self-checking program, the meter display will show the total active
energy (kWh)
Click the button, the LCD display will scroll the
measurements.
1
1-1
1-2
2
3
4
5
6
7
8
9
10
11
12
MID Approved B and D
Measures kWh, Kvarh, KW, Kvar,
KVA, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP
& EXP
Two pulse outputs
RS485 Modbus
Din Rail one Module width (18mm)
45A direct connected
5 Amp C.T operated
Better than Class 1 accuracy
Total active energy(kWh)
Display format:0000.00
Import active energy(kWh)
Display format: 0000.00
Export active energy(kWh)
Display format: 0000.00
Voltage (V)
Current (A)
Active power (W)
Frequency (F)
Power factor (PF)
Modbus Address or Primary address
Default: 001Baudrate Default : 9600bps
Parity
Even/Odd/None are optional
Primary current 1A-9999A
Default: 5 (sample shows 100A)
CT 2
Secondary current 5A
Software version
Ref. A-45Series.06.2021