Parameter Setting
• Some parameters are activated/deactivated depending on the model or setting of
other parameters. Refer to the descriptions of each item.
• [MD] key: Move to next item after saving / Return to RUN mode after saving (≥ 3 sec)
[◀] key: Select parameter / Move digits / Return to the upper level without saving (≥ 2
sec) / Return to RUN mode without saving (≥ 3 sec)
[▲], [▼] key: Select parameter / Change setting value
• Return to the upper level without saving when there is no key input for more than 30
seconds.
• The range in parentheses '( )' is the setting range when the set value of the 'input
specification' parameter is used with one decimal point.
• Recommended parameter setting sequence: Parameter 2 group → Parameter 1 group
→ SV setting mode
■ Parameter 1 group
Parameter
Display Default Setting range
1-1 SV2 setting
0 Refer to 'Input Type and Using Range'.
SU-2
Event 1 alarm
1-2
10 Refer to 'Input Type and Using Range'.
temperature
AL1
Event 2 alarm
1-3
temperature
AL2
10
1-4 LBA time
LBA
600
Alarm output
1-5
2 1 to 100 (0.1 to 100.0) ℃/℉
hysteresis
AHYS
Proportional
1-6
#0 0.0 (ON/OFF control) to 100.0%
band
P
1-7 Integral time
0 0 (OFF) to 3,600 sec
I
1-8 Derivative time
0 0 (OFF) to 3,600 sec
D
1-9 Control cycle
T
20
1-10 Hysteresis
2 1 to 100 (0.1 to 100.0) ℃/℉
HYS
Input
1-11
0 -49 to 50 (-50.0 to 50.0) ℃/℉
correction
IN-B
1-12 Manual reset
)0 0.0 to 100%
REST
1-13 RAMP up time
RAPU
10
1-14 RAMP down time
RAPD
10
1-15 Lock
LOC
OFF
■ Parameter 2 group
Parameter
Display Default Setting range
2-1 Input spec.
KCaH Refer to 'Input Type and Using Range'.
IN-T
2-2 Event 1
EU-1
AL-1
2-3 Event 2
EU-2
AL-2
2-4 Alarm option
AL-T
AL-A
Auto tuning
2-5
mode
AtT
TVN1
2-6 PID type
PIDT
PIdS
Control output
2-7
mode
O-FT
HEAT
Temperature
2-8
?C ℃, ℉
unit
UNIT
2-9 SV high limit
1300 Within input range
H-SC
2-10 SV low limit
L-SC
`00
2-11 Decimal point
0 0, 0.0, 0.00, 0.000
DOT
Transmission
2-12
output high
FS-H
1300
limit
Transmission
2-13
output low
FS-L
`00
limit
2-14 RAMP function
OFF OFF, ON
RAMP
2-15 Comm. speed
BPS
2400
Comm.
2-16
address
ADRS
01
2-17 Lock
OFF OFF, ON: Parameter 2 group lock
LOC
[Option output 2: Event model]
Refer to 'Input Type and Using Range'.
[Relay, SSR drive output model]
0 to 999 sec
[Relay, SSR drive output model]
1 to 120 sec
• Set to a small value in SSR drive
output models. (e.g. 2 sec)
1 to 99 min
OFF
ON: Parameter 1 group lock
ON1: Parameter 1 group + [AT] key lock
AL-0: Off
AL-1: Deviation high limit alarm
AL-2: Deviation low limit alarm
AL-3: Deviation high, low limit alarm
AL-4: Deviation high, low reverse alarm
AL-5: Absolute value high limit alarm
AL-6: Absolute value low limit alarm
SBA: Sensor break alarm
LBA: Loop break alarm (LBA)
[Option output 2: Event model]
Same as 2-2 Event 1
AL-A: Standard alarm
AL-B: Alarm latch
AL-C: Standby sequence
AL-D: Alarm latch and standby
sequence
TUN1: Tuning based on SV
TUN2: Tuning based on 70% of SV
PID.S: Low speed response
PID.F: High speed response
HEAT: Heating, COOL: Cooling
• Please set according to control
application. Do not change the
settings during operation. It may result
in fire or accidents.
Refer to 'Input Type and Using Range'.
[Option output 2: PV Trans. model]
Within input range
Refer to 'Input Type and Using Range'.
[Option output 2: Comm. model]
2400, 4800, 9600 bps
[Option output 2: Comm. model]
1 to 99
SV2 Setting
It is possible to control an additional temperature value at a desired range by using SV2.
Connect a contact signal (under 5 VDC
the range where the signal turns ON.
The internal temperature of an electric oven may drop rapidly if the door is opened
while the oven is maintaining a specific temperature. Set SV2 to a higher value than SV,
and input a signal to the external terminal (SV2 IN), to quickly raise the temperature.
Temperature
Condition
-
2-2/3 Event
1/2: AL-1 to 6
RAMP Up/Down Time
2-2/3 Event
1/2: LBA
2-2/3 Event
The ramp function can delay the rate of temperature rise/fall. If the SV value is changed
1/2: AL-1 to 6
during stabilized control, the temperature of the controlled target will rise/fall during
-
ramp up/down time. The ramp function activates when the power is reset or when the
SV value is changed during stable control.
1-6
Temperature
Proportional
band: > 0.0
Changed SV
1-6
Initial SV
Proportional
band: 0.0
RAMP
-
up
time
1-6
Proportional
band: > 0.0
1-7/8
Integral/
derivative
When delaying the rise of initial control temperature or changing the SV during
time: 0
stable control, it is possible to delay temperature rise. Set the ramp up time
2-14 RAMP
longer than the temperature rise time (tu) when not using the ramp function.
function: ON
Temperature
-
Changed SV
Initial SV
Condition
RAMP
-
down
time
-
Delays declining temperature. Set the ramp down time longer than the
temperature decline time (td) when not using the ramp function.
Auto Tuning Mode
2-2/3 Event
Execute auto tuning after select the mode which is suitable for user environment by
1/2: AL-1 to 6
refering to the following desciption.
TUN1
-
Auto tuning
Temp.
-
SV
-
Executes auto tuning based on SV.
-
-
-
2-1 Input
spec. :
Analog
-
-
-
-
-
, 250 ㎂) at the external terminal, to operate in
ᜡ
SV 2
SV
External Terminal
(SV2 IN) ON
: Not using ramp function
: Using ramp function
tu
tu
RAMP up time
RAMP up time
: Not using ramp function
: Using ramp function
td
RAMP down time
TUN2
Auto tuning
Temp.
SV
70%
Time
Executes auto tuning based on 70% of SV.
Time
Time
Time
Time