Notes:
- For XM678D Version 2.5, probes are Retail Solutions type.
- The same Engineering Unit must be used in the PA4 and P20 parameters as set in the device. See example
below:
•If a PP11 transducer is connected to an XM678D, Prn set to rEL and PMU (PNU in device) set to Bar, the ff.
procedures should be done:
a. PA4= -0.5
b. P20= 11
•To change the pressure reading on screen from bar to psi, the ff. procedures should be done in order:
a. Set PNU to psi
b. Set PA4= -7
c. Set P20= 161
Document Part # 026-4240 Rev 0 10-FEB-2015
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively "Emerson"), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does
not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.
026-4240 10-FEB-2015 Emerson is a trademark of Emerson Electric Co. ©2015 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.
This document may be photocopied for personal use.
Join Emerson Retail Solutions Technical Support on Facebook. http://on.fb.me/WUQRnt
Page 9 of 9