Section 4: Input and Output Data
November 2021
4.2.4

Actual Speed Value

Register number: 260, address 0103
Data format: 16 bit, only the lowest 8 bit (Bit 7: Direction OPEN; Bit 6 - 0 : 0 - 100
corresponding to 0 - 100%) are in use.
Other bits are reserved for future use and have to be set to zero.
4.2.5

External Actual Value

Only with Option PID-Controller
Register number: 261, address 0104
Data format: 16 bit, only the lowest 10 bit (0 - 1023) are in use.
Other bits are reserved for future use and have to be set to zero.
4.2.6

Status 2

Register number: 262, address 0105
Data format: 16 bit (Bitfield)
Table 9.
Bit no.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
NOTE:
Using parameter P15.6 it is possible to assign alternative output-functions to "Status 2".
12
Installation, Operation and Maintenance Manual
Structure
Description
Function
Bit = 0 Bit = 1
Dig. Output 1
-
Dig. Output 2
-
Dig. Output 3
-
Dig. Output 4
-
Dig. Output 5
-
Dig. Output 6
-
Dig. Output 7
-
Dig. Output 8
Dig. Input 1
-
Dig. Input 2
-
Dig. Input 3
-
Dig. Input 4
-
Dig. Input 5
-
PHASE SEQUENCE
-
FC ERROR
-
FAILSAFE ERROR
-
Hex
Hex
Hex
Corresponding binary output enabled.
Corresponding binary input enabled.
Phase Sequence Error: wrong phase order, phase failure,
total failure, asymmetry.
FC Error: Error in power supply or frequency converter (if present).
Failsafe-Unit not ready (if present).
VCIOM-16741-EN Rev. 0
Input and Output Data