Wall-Mounted Dewpoint Sensor
•
Set the Low End Point field to 0.
•
Set the HighEnd Point field to 5.0.
•
Set the Low Eng. Units field to 0.
•
Set the High Eng. Units field to 80.
•
Set the Low End Limit field to -0.5.
•
Set the HighEnd Limit field to 6.5.
Analog Input Screen - Set Sensor Properties
REFLECS
1. Log in to the controller.
REFLECS Login Screen
2. From the Main Menu, select 4 -Sensor
Control.
Product Information Sheet
49
REFLECS Main Menu Screen
3. From the Sensor Control screen, select 2 -
Setup.
Sensor Control Screen
4. From the Select Sensor screen, choose the
sensor you wish to set up:
Select Item Screen
5. Once you select a sensor, the Sensor Setup
screen opens. Enter a name for the sensor in
the Name field (for example, DEWPOINT)
and set the Type field to Linear by using the
scroll keys or pressing the red button + the
(L) button.
Sensor Control Screen
6. Press 0 to go back to the Sensor Control
screen. Select 3 -Setpoints and then choose
the sensor to set Gain and Offset.
210-2002