To replace the battery:
1.
Turn off all connected loads, then turn off the UPS (batteries are NOT
hot-swappable).
2.
Use a Phillips head screwdriver to remove the two top cover screws from
the back of the UPS.
3.
Slide the top panel backward 1/2" (13mm). Slide the front panel upward,
then pull outward to remove it.
4.
Gently pull the batteries out of the UPS.
5.
Remove the black wire from the negative (-) terminal and the red wire from
the positive (+) terminal.
6.
Verify that the replacement battery matches the dimensions and battery
type in the Specifications section below.
7.
Connect the battery leads to the new batteries. Be sure to reconnect the
red wire to the positive (+) terminal and the black wire to the negative (-)
terminal.
Note: Small sparks may occur at the battery connectors during
reconnection.
8.
Slide the batteries into the UPS.
9.
Reposition the front panel and slide downward until it slides into place.
Slide the top panel forward until flush with the front panel. Reinsert the two
top cover screws removed in Step 2.
Dispose of the old batteries properly at an appropriate recycling facility.
T
ROUBLESHOOTING
If the UPS malfunctions during operation, check the following chart for proper adjustment. For further assistance, please contact your local Emerson Network Power representative.
Problem
Utility power is normal, but LED 1 is not illuminated.
LED 2 flashes (amber) every 3 seconds, but there is
no output power.
Alarm buzzer beeps continuously although utility
power is normal.
UPS does not provide expected backup time.
The UPS is on and connected to input power, but fails
to operate properly.
S
PECIFICATIONS
Capacity (VA/W)
Net Weight, lb. (kg)
Shipping Weight, lb. (kg)
Dimensions - W x D x H, in. (mm)
On-Line Input Voltage
On-Line Frequency
Output Voltage (Mains Normal)
Output Voltage (Battery Operation)
On-Battery Wave Form
Battery Type - VDC x Ah x Quantity
Typical Recharge Time
Battery Run Time* - Full Load
Battery Run Time* - Half Load
Audible and Visual
Backup Outlets
Surge Outlets
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Operating / Storage Relative Humidity
EMI Classification
Agency
* Battery run time may vary depending on load
© 2008 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners.
SL-23301_REV0_04-08
ATTERY
The UPS may not be turned on.
The power cord may not be connected properly.
The upstream input circuit breaker may be tripped.
Battery voltage may be too low.
The UPS may be overloaded (check LED 2).
The UPS battery reached end of life.
Utility power may be outside the unit's operating range.
Model Number
PSA1000MT3-120U
1000/600
23.8 (10.8)
26.0 (11.8)
12V x 7Ah x 2
Safety
Transportation
Steps 2 and 3
Possible Causes
PSA1500MT3-120U
1500/900
27.8 (12.6)
30.0 (13.6)
5.8 x 14.2 x 9.2 (147 x 360 x 234)
84-140VAC
50/60Hz ±5Hz
Typical 97-129VAC
120VAC ±5%
Stepped sinewave
12V x 9Ah x 2
6-8 hours to 90%
6 minutes
12-13 minutes
Audible alarm / LED
NEMA 5-15R (6)
NEMA 5-15R (2)
32 to 104 (0 to 40)
5 to 104 (-15 to 40)
0%-90%, non-condensing
FCC Part 15 Class B
UL 1778, c-UL Listed
ISTA Procedure 1A Certification
Steps 4 and 5
• Press the On/Off button to turn on the UPS.
• Connect the power cord securely into a wall outlet.
• Reset the input circuit breaker.
• Recharge the UPS for 8 hours.
• Disconnect some equipment from the UPS.
• Replace the internal battery.
• If utility power is normal, try reconnecting input