7 Technical data
DANGER Danger if the relevant regula-
tions for electrical installations are not ob-
served.
Observe the safety rules of electrical engineering.
Before taking off covers and before installing the
electrics, shut down all supply circuits, switch off
mains fuse, check that no voltage is present, se-
cure against being accidentally switched back on
and position a visible warning sign.
Only connect the unit to a permanent electrical
installation. Select cable type and cross-section
in accordance with DIN VDE 0298-4 → Technical
data.
A mains isolation device with contact openings of
at least 3 mm at each pole is mandatory. Make
connections according to wiring diagram.
The unit may only be operated using the voltage
and frequency shown on the rating plate. Con-
nect PE conductor and check the connection.
Check protective-conductor opening on housing
(VDE 0100-600, VDE 0105-100).
Only operate the unit when it is completely in-
stalled.
Modifications and alterations are not permitted
and release the manufacturer from any guaran-
tee obligations and liability.
Do not put a damaged unit into operation and do
not allow it to be operated until repaired.
The degree of protection stated on the rating
plate is only guaranteed if installation is under-
taken correctly and if the connection cable is cor-
rectly guided into the housing.
CAUTION Exercise caution when hand-
ling packaging materials.
Store packaging material out of the reach of chil-
dren (risk of suffocation due to swallowing).
7 Technical data
Rated voltage
Power frequency
Maximum loading
(inductive load)
Maximum loading
(ohm resistive load)
Max. backup fuse
Max. power loss
Radio interference sup-
pression (EN 55011)
Max. cable cross-sec-
tion
6
230 V AC
50 Hz/60 Hz
0.4 A
10 A
25 A (gL)
approx. 6 W
VDE 0875, interference
level N
6 mm²
Max. cable cross-sec-
tion for TB/auxiliary
switch
Degree of protection
Protection class
Type of installation
Weight
Dimensions (WxHxD)
Ambient temperature
For more technical data → rating plate.
8 Installation, electrical connec-
tion
Installation instructions
• Only install unit on a dry, flat surface. Do not
distort housing. Any installation position can be
selected.
• Select installation location outside of traffic
area. Protect unit from direct sunlight. Ensure
sufficient heat dissipation.
Installation
1. Loosen both of the housing cover screws and
remove the housing cover.
2. Pull off both retaining brackets and remove the
switch insert from the housing.
3. Break out cable lead-throughs at the knockout
points in the housing, according to the number
of cables, and insert cable grommets. Insert
the grommets so that they fit tightly against the
housing and around connection cable cables.
4. Mount the lower part of the housing on the
wall. Suitable mounting material is to be
provided by the customer.
5. Guide the connection cables into the housing
through the grommets, check for leak tight-
ness.
6. The connection of the mains voltage must be
at the top, the connection of the motor must be
at the bottom. Swapping the input and output
sides is not permitted.
7. Wire motor protection switch in accordance
with wiring diagram.
The connection of the mains voltage must
be at the top, the connection of the motor
must be at the bottom. Swapping the input
and output sides is not permitted. Only con-
nect thermal contact to terminals marked with
TB.
2.5 mm²
IP 55
II
Surface-mounted
0.6 kg
80 x 135 x 96.5 mm
-25 ... 40 °C