AGS Merlin 1000S+i Panduan Pengguna & Instalasi - Halaman 8
Jelajahi secara online atau unduh pdf Panduan Pengguna & Instalasi untuk Pengontrol AGS Merlin 1000S+i. AGS Merlin 1000S+i 9 halaman. Gas & electric utility controller
Merlin 1000S+i
Gas & Electric Utility Controller
1) [POWER] Mains Input 110-120VAC Single Phase.
2) [GAS VALVE] Gas Solenoid Valve Power Output, 110-120VAC, Max 3A.
3) [ELECTRIC CONTACTOR] Electric Contactor Power Output, 110-120VAC, Max 3A.
4) [BMS OUT] Building Management System output contacts.
Normally Closed, Common and Normally Open. Max.1A @ 110-120VAC.
5)
[EM REMOTE] Remote EM Stop buttons and Fire Alarm input wired in series VOLT FREE
(Purchased separately).
6) [GAS DETECTOR] Methane, CO or LPG Detector, power supply and VOLT FREE
(Purchased separately).
7) [FS1/2/3/4] Fan Switch output (purchased separately).
For wiring instruction see Fan Switch user manual.
8) [CO2 MONITOR] CO2 Monitor (purchased separately). VOLT FREE
9) [12VDC] Permanent 12VDC output when there is power at the panel. 50mA max
Panel Net Weight: 1187g
Panel Dimensions: (W) 10" x (L) 7" x (D) 2.4"
MAINS AND LOW WIRING SHOULD NOT RUN IN THE SAME CONDUIT AS PER THE LOW VOLTAGE DIRECTIVE
Rev: 04 Date: 22-10-18
1000S+i WIRING
PLEASE NOTE:
User & Installation Manual
8