AGS Mini Merlin LPGCO v2-FL Pengoperasian & Pemeliharaan Instalasi - Halaman 15
Jelajahi secara online atau unduh pdf Pengoperasian & Pemeliharaan Instalasi untuk Detektor Gas AGS Mini Merlin LPGCO v2-FL. AGS Mini Merlin LPGCO v2-FL 16 halaman. Dual gas detector
Mini Merlin Installation, Operation & Maintenance
Specification
General
Model:
Target Gases:
Size: (H x W x D)
Housing Material:
Mounting:
Weight:
User Interface
Display:
Screen Brightness:
Visual Indicators:
Audible Alarm:
Buttons:
Language:
Power Supply
Power Consumption:
AC Power:
Internal Fuse:
Equipment
Overvoltage Category:
Pollution Degree:
Relays
Volt Free BMS relay output:
Environmental
Ingress Protection:
Operating:
Storage:
Altitude Rating:
Wiring
Typical
Approvals
Electrical Safety and
Electromagnetic Compatibility
Sensor Specification
Indicating
Gas Sensor
Electrochemical Sensors
Carbon Monoxide (CO)
0-999ppm
Semiconductor Sensors
Propane (LPG)
0-20% LEL
Rev: 03 05-22
Mini Merlin LPGCO v2 FL
LPG & CO
5.95 x 4.37 x 1.97" (151 x 111 x 50mm)
ABS PA765 (Flame Rating UL94 V-1)
Safe Zone - Indoor use - Wall Mounted
12.24oz (0.347kg)
1.8" TFT
Non-Adjustable
TFT visual. Green: Normal; Yellow: Pre-Alarm; Red: Alarm
>70dB @ 3.28ft (1m). Quiet conditions.
Multi-Function – Initial Start / Reset / Circuit Test
English
3W max
100-120V~ 50/60Hz
Anti-Surge 3.15A 250Vac
II
2
0.5A switching current (resistive load)
Not Formally Evaluated
-10 ~ 50°C / 14 ~ 122°F 30 ~ 80% RH (non-condensing)
-25 ~ 50°C / -13~122F° up to 95% RH (non-condensing)
2000m
Min. 18AWG / 75°C min / Tinned copper.
UL61010-1/2012/R:2019-07.
CAN CSA C22.2 No. 61010-1-12/A1:2018-11
EMC EN 61326-1:2013
Response
Steps
Range
(t90)
1
<60s
0.1
<30s
▲ Rising Alarm ▼Falling alarm *EOL – Expected Operational Life
Recovery
Alarm: 1
(t10)
(Pre alarm warning)
<60s
▲20ppm
<30s
▲8% LEL
Alarm: 2
(Years)
▲35ppm
▲10% LEL
*EOL
5
10
15