AGSTECH 300L Panduan Pengguna - Halaman 6

Jelajahi secara online atau unduh pdf Panduan Pengguna untuk UPS AGSTECH 300L. AGSTECH 300L 7 halaman. Dc12v/24v/48v with 2~6 channels

5. LED Indications

The system monitoring provides 8 LEDs to indicate the status of the DC UPS.
Front Panel Display
LED SIGNAL
I/PWR
(Input Power)
O/PWR
(Output Power)
CHG
(Charging)
BAT
(Battery)
 Functional Description of System Monitoring
The I/PWR green LED lights up when AC I/P is good and charger can provide
current to the battery. In case of blackout or burning of I/P fuse, the I/PWR
yellow LED lights up, the Green LED goes out and the error will be reported
via the dry contact signal.
The O/PWR green LED lights up when the O/P power is normal, the O/PWR
yellow LED lights up when the O/P power is abnormal, or short circuit, or the
O/P is overload.
The CHG green LED lights up when the charging voltage on battery reach full
level, the CHG yellow LED lights up when the charger is full ON for providing
current to the load or battery. It is normal when CHG yellow LED lights up all the
time when the load level is over 60% of full load.
The BAT red LED lights up when the battery is not well connected or when any
one of the battery is fail, the BAT yellow LED lights up when the battery voltage
is low and the error will be reported via the dry contact signal.
LED#
COLOR
Green
Yellow
Green
Yellow
Green
Yellow
Red
Yellow
Page 6 of 7
Operating Status
AC Normal
Power Failure
DC Normal
Overload or Short Circuit
Fully Charged
Charging or with loading
Battery Replacement
Battery Low
VER.: 1.1