Table of distances from combustibles
Stove Type
Sherford Slimline 5 SE
It may be necessary to shield a beam or mantle piece from the heat. The single wall flue must
be at least 3 times its diameter away from combustible materials i.e. 150mm (6") flue 450mm
(18") away from combustible materials.
Be careful not to place furniture or other combustible material too close to the stove.

Register plates

Chimneys without continuous flue to the top , must have the register a plate made of 1.5mm
steel treated to prevent corrosion (BS8303 part 3 9.5)
Register plates made of fireboard may only be used if a liner or flue runs from the top of the
stove to the top of the chimney without a break. Always check the current building regulations.
Flue Connections and Outlets
Dean Stoves can be flued from the top and the back, or with a vertical back box. Horizontal
flue from back of stove should not exceed 150mm.
All flue connections must be sealed. Doors in the register plate must be present or a soot box
fitted in the back or side of the fireplace to enable access to clean the chimney when the stove
is installed without a flue liner.
If the chimney has been lined and cannot be swept through the stove an access door on the first
length of flue must be installed for cleaning access.
The Sherford Slimline 5 SE model requires a 125mm (5") first length of flue then stepping up
into a minimum of 150mm (6") liner. When the Sherford Slimline 5 SE has a smoke except air
slider fitted the flue liner can be reduced to 125mm (5"). We strongly advise a 150mm (6")
flue liner be fitted when possible.
Minimum from back of
appliance to combustibles
400 mm (with optional heat
shield)
1000 mm (without heat
shield)
8
Minimum from side of
appliance to combustibles
500 mm