Adeunis RF MOTION V2 Panduan Referensi Teknis - Halaman 4

Jelajahi secara online atau unduh pdf Panduan Referensi Teknis untuk Aksesori Adeunis RF MOTION V2. Adeunis RF MOTION V2 15 halaman. 868 eu - lorawan/sigfox

1 R
EGISTERS

1.1 Generic registers

Size
Register
(bytes)
304
2
306
1

1.2 Applicative registers

Size
Register
Base
(bytes)
300
2
10
301
2
10
308
4
16
320
2
10
321
2
10
322
2
10
330
1
10
340
1
10
341
1
10
342
1
10
343
1
10
Base
Description
10
PIN code
Product
10
mode
Default
Description
value
Keep alive
8640 (24h)
period
Periodic
transmission
1
frequency
LED activity
0x4007F
Historization
1
frequency
Sampling/
acquisition
1800 (1h)
period
Sensor inhibition
30
for presence
(5 min)
detection
Presence alarm
0
activation
(OFF)
Alarm type for
0
brightness
(inactive)
High threshold
0
value
High threshold
0
hysteresis
Low threshold
0
value
Manage & optimize your assets & services
283, rue louis Néel 38920 CROLLES, France
Tél : +33 (0)4 76 92 07 77 E-mail : [email protected]
www.adeunis.com
Date: 02/12/2019
Default
Range
Value
(Min-Max)
0
(deactivat
0 - 9999
ed)
0: PARK
0
1: RUN
Min-Max Value
2 ... 65535
0 ... 65535
0-0xFFFFFFFF
1 ... 65535
0 ... 65535
1 ... 65535
0: not activated
1: activated
0: Inactive
1: Low threshold
2: High threshold
3: Both thresholds
0 ... 100
0 ... 100
0 ... 100
adeunis
®
Comments
PIN code used with ATPIN command.
Value 0 disables the PIN code.
In PARK mode, product is not using
Radio.
In RUN mode, product will
send/receive RF uplinks/downlinks.
Comments
X 10 seconds
Number of backups (history
logs) to be done before
sending a frame (thus
defining the sending period).
The value 0 is equivalent to
disabling the periodic mode.
Default: 4007F
Eco mode: 40070
Other values: reserved
Number of samplings to be
performed before saving in
the history logs
The value 1 is equivalent to
1 backup per reading
X 2 seconds
X 10 seconds
Correspond to the wait time
before reauthorizing
presence detection.
%
%
%
Page 4 / 15