JAGA ROOM THERMOSTAT JRT-100
INSTALLATION , SETTINGS & USE
Important info : The unit must be installed by a certified installer in accordance with the installation instructions and the local building codes. Please follow this instruction manual
and file it somewhere safe! The unit must always be accessible for maintenance and inspection. . Jaga n.v. cannot be held liable for damage due to non-compliance with this manual.
PRODUCT DESCRIPTION
– 2-pipe and 4-pipe connection :
– 4-pipe connection : Heating / Cooling / Auto-change-over
– 2-pipe connection : Heating / Cooling
– automatic or manual fan speed control
– mounting on mounting box with screws
– programmable time zones (5+1+1): Monday - Friday (1-5), Saturday (6), Sunday (7)
– 0-10V exit
– valve control with 24V AC / DC thermoelectric motor
– possibility to run the fan once the"set point" has been reached (manual operation)
TECHNICAL DATA
POWER SUPPLY
POWER CONSUMPTION
SETTING RANGE
AMBIENT TEMPERATURE
RELATIVE HUMIDITY
BACK-LIGHT
SENSOR
ACCURACY
SAFETY CLASS
HOUSING
DIMENSIONS
8.6
8.6
M
CE MARK
The CE mark indicates hat this device meets the basic requirements of the directive on:
• EN 61000-6-3:2007+A1:2011
• EN 61000-3-2:2006+A1:2009+A2:2009
• EN 61000-3-3:2008
• EN 61000-6-1:2007
24V AC/DC
200 mA
+10 ... +40°C
0 ... +40°C
85% max
Blue
NTC 10K, 3950 ohm at 25 ° C
+ 1°C (+0.5°C)
IP30
ABS with UL94-5 flame retardant plastic
6
JAGA NV | ROOM THERMOSTAT JRT-100 | MANUAL | 15 JANUARI 2024, 11:11 | V.5.2
JRT-100
DEVICE INSTALLATION GUIDELINES
Install the room thermostat at approximately 1.5 m above
the floor against an interior wall and opposite the heating
source if possible. Avoid the outer walls, draft coming
from the windows and doors, direct sunlight and other
heat sources such as TVs, wall or table lamps, fire places,
heating pipes, etc. Ensure that the locking mechanism on
the bottom of the thermostat is easily accessible.
1.4 3.4
Mount the JRT.100 Room thermostat in a flush mounting
box with screw holes at a 60 cm distance from the center.
Minimum depth 45mm, (the depth depends on the wiring).
The internal dimensions of the box should be at least
Ø60mm or 50x50mm.
MANUAL
www.jaga.com/downloads/Briza/Man-
ual_JRT100.pdf
/ 8751.050012
1.5 m
4.6
6
EN
1.5
13