Jakka Pro Manual - Halaman 5

Jelajahi secara online atau unduh pdf Manual untuk Pengontrol Jakka Pro. Jakka Pro 6 halaman.

MANUAL for JAKKA PRO CONTROLLER
11.3 BMS ADDRESS SETTING
7. ÖZEL KONTROL FONKSİYONLARI
11.4 SETPOINT LIMIT OPERATIONS
the range of 5-35 °C, by the ▲ and ▼ keys.
(Default value : 30 °C)
Note 1: Minimum Limit can not be greater than maxi-
mum limit.
Note 2: Maximum Limit can not be lower than mini-
mum limit.
11.5 ELECTRICAL HEATER CONTROL SETTINGS
Electrical heater can be controlled according to the
two different temperature value.
01 : Controlled Depending on Room Temperature :
Electrical heater is controlled by the sensor on the pa-
nel or return air temperature sensor. Control is active
without any adjustment. ( Default )
02 : Controlled Depending on Outdoor Temperature:
Electrical heater is controlled according to the
"Outdoor Air Temperature Sensor" connected on the
main controller. Enter the service menu to activate the
control according to the outdoor air temperature.
Control Activate
After logging into the servi-
ce menu, using the MODE
and FAN keys, select the 00.
parameter.
Use the ▲ key to increase
the address, use the ▼ key
to decrease the address.
Setting range 0-247.
Minimum
Limit:
Firstly,
"Main Parameter" must be
replaced as 2, by the MODE
and FAN keys.
Secondly, "Auxiliary Para-
meter" can be selected in
the range of 5-35 °C, by the
▲ and ▼ keys. (Default
value: 05 °C)
Maximum Limit:
Firstly, "Main Parameter"
must be replaced as 3, by
the MODE and FAN keys.
Secondly, "Auxiliary Para-
meter" can be selected in
Outdoor Control Activate:
Firstly, "Main Parameter"
must be replaced as "9", by
the MODE and FAN keys.
Secondly, "Auxiliary Para-
meter" must be replaced as
"2", by the ▲ and ▼ keys.
the range of 0-20 °C, by the ▲
Set
and ▼ keys.
(Default value : 15 °C)
Note: If outdoor air temperature value lower than
value set in the service menu, the heater stages is
activated.
11.6 DATE SETTINGS
Note: When the specified steps are correctly completed,
device will choose day of week correctly.

11.7 FACTORY DEFAULT

This parameter used to correct changes made by mista-
When the device returned factory defaults, parameter
value is set to "0" automatically. (Default value = 0)
Setpoint Setting:
Firstly, "Main Parameter"
must be replaced as "10",
by the MODE and
FAN
keys.
Secondly, "Auxiliary Para-
meter" must be selected in
1. Firstly, "Main Parameter"
must be replaced as 12, by
the MODE and FAN keys.
Secondly, "Auxiliary Para-
meter" must be set to the
desired day value.
2. Firstly, "Main Parameter"
must be replaced as 13, by
the MODE and FAN keys.
Secondly, "Auxiliary Para-
meter" must be set to the
desired month value.
3. Firstly, "Main Parameter"
must be replaced as 14, by
the MODE and FAN keys.
Secondly, "Auxiliary Para-
meter" must be set to the
desired year value.
ke.
Firstly, "Main Parameter"
must be replaced as 15, by
the MODE and FAN keys.
Secondly, "Auxiliary Para-
meter" must be replaced as
1, by the ▲ and ▼ keys.