Airflow DUPLEXVENT DV145SE Petunjuk Pengoperasian, Pemeliharaan, dan Teknis
Jelajahi secara online atau unduh pdf Petunjuk Pengoperasian, Pemeliharaan, dan Teknis untuk Kipas angin Airflow DUPLEXVENT DV145SE. Airflow DUPLEXVENT DV145SE 17 halaman. Low-energy ventilation unit with heat recovery and demand-controlled automatic melting
© Air ow
1.09.600E
17.6.2013
1
Extract air fan
(behind protective cover)
2
Supply air fan
(behind extract air duct)
3
Outdoor air fi lter F7
4
Heat recovery cell
5
Summer/winter damper
6
Outdoor air fi lter G4
7
Extract air fi lter G4
8
Post-heating radiator
(behind extract air duct)
9
Safety switch
10 Additional heating radiator
(behind extract air duct)
11 Control panel DIGIT SED
12 Carbon dioxide sensor
13 Humidity sensor
Low-energy ventilation unit with heat recovery
and demand-controlled automatic melting
Operating, maintenance and
technical instructions
9
8
2
10
7
11
12
13
TECHNICAL DATA
Electrical connection
Degree of protection provided by enclosures
Fans
Extract air
direct current (DC)
Supply air
Heat recovery
Heat recovery bypass
Electric post-heating unit (standard)
Additional heater
Fans
Supply air
Extract air
Weight (with packaging)
Ventilation power adjustment
Options
DV145SE
The fi gure shows the R model
230 V, 50 Hz,
11.9 A (plug)
≈
IP34
150 dm
/s 100 Pa
3
140 dm
/s 100 Pa
3
Cross-counter flow heat recovery cell, > 80%
Automatic
900 W, 3.9 A
1500 W, 6.5 A
G4 and F7
G4
88 kg
- control panel control
CO
and %RH control
-
2
- remote monitoring control (voltage signal)
- CO
sensor
2
- %RH sensor
- Insulated attic fl oor penetration plate
Base
-
6
3
1
5
4