HOW TO ACTIVATE USER PROGRAMMING MODE
·
Press the button DOWN and keep it pressed for 3 seconds.
The display will show the message:
·
Enter the Password UP-DOWN-UP-DOWN-UP
The display will show the message:
HOW TO MODIFY A VALUE
Scroll between the programmable values using the UP/DOWN buttons.
In order to modify a value, press ENTER and keep it pressed for 2 seconds, until the cursor will start blinking over
the value that can be modified.
Modify the value using the UP/DOWN buttons.
Confirm the modified value by pressing ENTER for 2 seconds, until the cursor will disappear. At this point the new
value will be saved.
HOW TO RETURN TO NORMAL MODE
Press the buttons UP and DOWN simultaneously.
PARAMETER 1:
NOMINAL OUTPUT VOLTAGE
Programmable values:
12-24-36-48-72-80-96-120 Volts
Default value:
Nominal voltage of the charger
NOTE:
This parameter should be changed only after replacing the control board of the charger.
PARAMETER 2:
NOMINAL CHARGING CURRENT
Programmable values:
From 10 to 400 Amps
Default value:
Nominal output current of the charger
NOTE:
This parameter should be changed only after replacing the control board of the charger.
PARAMETER 3:
GASSING VOLTAGE
Programmable values:
from 2.35 to 2.50 V/Cell
Default value:
2.40 V/cell
NOTE:
This charging algorithm of the Black charger is adaptive, so it's capable of adjusting the charging curve even if the
gassing voltage of the battery deviates significantly from the programmed value. For this reason, this parameter should be
modified only when using non-standard batteries, or if the operating temperature is extremely low or high.
When a battery temperature probe (optional) is connected, the charger compensate the gassing voltage VS temperature of
the electrolyte.
PARAMETER 4:
MAXIMUM VOLTAGE
Programmable values:
from 2.40 to 2.80 V/Cell, or DISABLED
Default value:
2.80 V/cell
NOTE:
This parameter sets a maximum limit for the cell voltage. If this limit is reached, the charge is terminated and a
specific error message is given.
Press the button DOWN and keep it pressed for 3 seconds
The display will show the message:
ACTIVATE PROGRAM MODE
HOW TO ACTIVATE USER PROGRAMMING MODE
Press the button DOWN and keep it pressed for 3 seconds
The display will show the message:
Enter the Password UP-DOWN-UP-DOWN-UP
The display will show the message:
Enter the Password UP-DOWN-UP-DOWN-UP
The display will show the message:
HOW TO MODIFY A VALUE
Scroll between the programmable values using the UP/DOWN buttons.
HOW TO MODIFY A VALUE
In order to modify a value, press ENTER and keep it pressed for 2 seconds, until
the cursor will start blinking over the value that can be modified.
Scroll between the programmable values using the UP/DOWN buttons.
Modify the value using the UP/DOWN buttons.
In order to modify a value, press ENTER and keep it pressed for 2 seconds, until
the cursor will start blinking over the value that can be modified.
Confirm the modified value by pressing ENTER for 2 seconds, ultil the cursor will
disappear. At this point the new value will be saved.
Modify the value using the UP/DOWN buttons.
Confirm the modified value by pressing ENTER for 2 seconds, ultil the cursor will
disappear. At this point the new value will be saved.
HOW TO RETURN TO NORMAL MODE
Press the buttons UP and DOWN simultaneously.
HOW TO RETURN TO NORMAL MODE
Press the buttons UP and DOWN simultaneously.