Power supply
1.
2.
The control unit supply cable should be able to be switched off and
have a separate fuse (max. 16 A).
Probe
1.
2.
Standard screened cable 2 x 0.5 mm² can be used to extend the
probe cable. The maximum length of the extension cable is 50 m.
Output
The output signal of RG 210 is made available via a voltage-free re-
lay contact (1 changeover contact).
1.
2.
CAUTION
The switching contact may be destroyed by voltage peaks when
inductive consumers are switched off.
RG 210
Connect the level switch to mains by means of a permanently
installed cable such as NYM-J 3 x 1.5 mm².
Route the mains cable through the upper rubber cable gland
into the black base of the control unit.
The phase must be connected to terminal L1 , the neutral con-
ductor to terminal N and the protective conductor to terminal PE.
Do not route the probe cable next to mains cables; danger of in-
terference.
Protect the probe cable from damage; use metal pipes, if re-
quired.
The probe cable(s) must be permanently installed.
Route it/them through the bottom rubber cable glands of the
black base and connect them to the corresponding "Probe" ter-
minal(s).
You do not have to ensure a specific polarity.
The connection cable must be permanently installed.
Route it through the middle rubber cable gland of the black base
and connect it to the corresponding "Release" terminals.
Use commercially available standard RC combinations such as
0.1 µF/100 Ohm for inductive consumers.
Installation and commissioning
15