Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Rentang KitchenAid KDRP707RSS - 30" Pro-Style Dual Fuel Range. KitchenAid KDRP707RSS - 30" Pro-Style Dual Fuel Range 16 halaman. 30" (76.2 cm) and 36" (91.4 cm) classic commercial-style dual fuel convection range with steam-assist
Gas Supply Line
Provide a gas supply line of ¾" (1.9 cm) rigid pipe to the
range location. A smaller size pipe on longer runs may result
in insufficient gas supply. Pipe-joint compounds that resist
the action of LP gas must be used. Do not use TEFLON
tape. With LP gas, piping or tubing size can be ½" (1.3 cm)
minimum. Usually, LP gas suppliers determine the size and
materials used in the system.
Flexible metal appliance connector:
If local codes permit, a new CSA design-certified,
4 - 5 ft (122 - 152.4 cm) long,
¾" (1.9 cm) I.D., flexible metal appliance connector may
be used for connecting range to the gas supply line.
A ½" (1.3 cm) male pipe thread is needed for connection
to the female pipe threads of the inlet to the appliance
pressure regulator.
Do not kink or damage the flexible metal tubing when
moving the range.
Rigid pipe connection:
The rigid pipe connection requires a combination of pipe
fittings to obtain an in-line connection to the range. The rigid
pipe must be level with the range connection. All strains must
be removed from the supply and fuel lines so range will be
level and in line.
Must include a manual shutoff valve:
The supply line must be equipped with a manual shutoff
valve. This valve should be located in the same room but
external to the range. It should be in a location that allows
ease of opening and closing. Do not block access to shutoff
valve. The valve is for turning on or shutting off gas to the
range.
A
A. Gas supply line
B. Shutoff valve "open" position
C. To range
†®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
8
®†
" (1.6 cm) or
B
C
Gas Pressure Regulator
The gas pressure regulator supplied with this range must be
used. The inlet pressure to the regulator should be as follows for
proper operation:
Natural Gas:
Minimum pressure: 6" (15.2 cm) WCP
Maximum pressure: 14" (35.6 cm) WCP
LP Gas:
Minimum pressure: 11" (27.9 cm) WCP
Maximum pressure: 14" (35.6 cm) WCP
Contact local gas supplier if you are not sure about the inlet
pressure.
Burner Input Rating - Altitude
Input ratings shown on the model/serial rating plate are for
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a
rate of 4% for each 1,000 ft (304.8 m).
Gas Supply Pressure Testing
Line pressure testing above ½ psi gauge (14" WCP)
The range and its individual manual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures greater than
½ psi (3.5 kPa).
Line pressure testing at ½ psi gauge (14" WCP) or lower
The range must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure
testing of that system at test pressures equal to or less than
½ psi (3.5 kPa).