Alke AP-2-FT Panduan Pengguna, Servis, dan Pemasangan - Halaman 10
Jelajahi secara online atau unduh pdf Panduan Pengguna, Servis, dan Pemasangan untuk Pemanas Alke AP-2-FT. Alke AP-2-FT 13 halaman. Atmospheric stainless-steel gas infrared heaters for use in well ventilated areas
Fault finding table
Trouble
Burner does not light.
Burner extinguishes
after lighting
Flames leave the
- confines of the burner,
- or are sooting,
- or a blue cloud is
under the reflector
The burner is only partly
glowing
The burner makes a lot
of noise after ignition or
after several minutes
The burner does not
work at minimum
position
Heater will not attain the
desired temperature
Declaration of conformity
We, Alke B.V., located in Scherpenzeel, The Netherlands, hereby declare that the AP series, marked
on their data plates with CE and with CE approval/production supervision by Kiwa (number 0063) are in
compliance with the following EU legislation:
-
Directive on appliances burning gaseous fuels (GAD) 2009/142/EC (ex 90/396/EEC)
-
Regulation on appliances burning gaseous fuels (GAR) 2016/426/EU
Scherpenzeel, 01-04-2018
Adri van Alphen
President
Version: April 2018
Action
•
Check if gas valve of the gas cylinder or gas line is open
•
Check if gas cylinder is empty
•
First ignition will take up to 60 or more seconds before gas is available
•
Check if the injector is blocked
•
Check if the gas pressure/gas quality is identical to the pressure
indicated on the data plate
•
Keep button safety device pressed for a longer period (up till 25
seconds)
•
Check if the thermocouple is connected properly to the gas safety
device
•
Check if the thermocouple tip is close to the flame
•
Thermocouple or magnetic coil of the safety device is broken.
•
Gas pressure lower than minimum requested
•
Heater not suspended at 15 degrees angle
•
Gas pressure is too high. Check the gas pressure with the data plate
•
Check if the gas pressure regulator is broken.
•
Wrong gas is used. Check data plate for the correct gas supply
•
Venturi/air inlet is blocked/dirty
•
Check the size of the venturi and injector with the table
•
Not enough fresh air available due to mounting situation
•
Air filter is dirty
•
Heater not suspended at 15 degrees angle
•
Wrong gas or pressure is used. Check data plate with the gas supply
•
Check if the injector or venturi are blocked or dirty
•
Check the injector and venturi size with the table
•
Check if pipe sizes or gas hoses have sufficient capacity
•
Check the setting of the thermostat
•
Wrong gas is used. Check data plate with the gas supply
•
Check if the venturi gauze is broken or damaged so the flame burns
inside the venturi tube
•
Gas pressure is not correct. Check the gas pressure with the data plate
•
Wrong gas is used. Check data plate for the correct gas supply
•
Check the size of the venturi and injector with the table
•
Sensor or wire thermostat is broken
•
Thermostat valve adjusting mechanism is blocked
•
There is insufficient heat in the building for heat loss (i.e., not enough
brooders).
•
The thermostat sensing bulb is incorrectly placed
•
The thermostat is out of calibration or broken
10
manual number: 0009 0420EN