7. FIELD SETTING

• Discharge the static electricity from your body before setting up the switches.
• Never touch the terminals or the patterns on the parts that are mounted on the
board.

7.1. Field setting buttons

• Remove the front panel of the outdoor unit to access the print circuit board of the
display unit.
Print circuit board buttons for various settings and LED displays are shown in the
figure.

7.2. Function settings

• Various functions can be set. Follow the setting method described in 7.2.1. and 7.2.2. to set as per the requirement.
Perform these settings after the indoor unit stops.
Table. Settings List
POWER/
No
Setting Item
MODE
Level 1
(9 times)
Low noise
1
mode setting
Level 2
(9 times)
Level 1
(9 times)
Level 2
Peak cut
(9 times)
2
mode setting
Level 3
(9 times)
Level 4
(9 times)
Sign "
": Lights off, "
": Lights on
7.2.1. Setting for Low noise mode
(1) Switch to "Local setting mode" by pressing [MODE] button (S134) for 3 seconds or
more.
(2) Confirm (POWER / MODE) blinks 9 times, and press [ENTER] button (S132).
PUMP
POWER/
ERROR
DOWN
MODE
(L1)
Blink
(9 times)
Sign "
": Lights off, "
": Lights on, () : Number of blinking
(3) Press [SELECT] button (S133), and adjust LED display as shown below. (Current
setting is displayed)
LOW NOISE
(L2)
LOW NOISE
Blink
MODE
Sign "
": Lights off
CAUTION
LED display
PUMP
LOW NOISE
ERROR
DOWN
(L1)
(L2)
Blink
Blink
Blink
Blink
Blink
Blink
LOW NOISE
PEAK CUT
(L2)
(L3)
(L4)
(L5)
(L3)
LED display part
Button part
PEAK CUT
(L3)
(L4)
(L5)
(L6)
(4) Press [ENTER] button (S132).
LOW NOISE
MODE
Sign "
": Lights off, "
(L6)
(5) Press [SELECT] button (S133), and adjust LED display as shown in below figure.
Level 1
Level 2
Sign "
": Lights off
The noise of Level 2 is lower than the one of Level 1.
Factory
Content
setting
By using the "Low noise mode", the limit of the
noise level will be set to decrease the noise
level. The mode comes in 2 levels which can
be set accordingly.
To turn on the mode, use the external input
connector (P580).
*By using this mode, the cooling/heating
performance may decrease.
*Depending on the operating condition, the
noise level may not decrease even if the Low
noise mode is on.
The capacity limit can be selected when
operating with the Peak cut mode. The
operation selection can be done by external
input connector (PA580).
The lower the level, the more the effect of
energy saving, but the cooling/heating perfor-
mance decreases.
LOW NOISE
(L2)
(L3)
": Lights on
PEAK CUT
(L4)
(L5)
(L6)
Blink
Blink
En-13