11. TEST RUN

11.1. Pre-test run check items

Before the test operation, refer to the figure and check the following items.
Is the outdoor unit securely installed?
Have you performed gas leakage inspection?
(Connection joints of various pipes (flange connection, brazing))
Is the heat insulation done completely?
(Gas pipe, liquid pipe, drain hose extension on indoor unit side, etc.)
Is the water discharging from drain without any problems?
Are the cables connected correctly?
Are the cables as per specifications?
Is the earth wire connected accurately?
Are there any obstacles blocking the suction gate, and outlet of
the indoor/outdoor units?
Have you filled the specified amount of refrigerant?
Are the stop valves of gas pipe and liquid pipe fully open?
Has the power been supplied to crankcase heater for more than 6 hours?
After checking that the above items are all in order, refer to "11.2. Test operation
method" to test operation the unit. If there are problems, adjust immediately and
recheck.

11.2. Test operation method

Be sure to configure test run settings only when the outdoor unit has stopped
operating.
• Depending on the communication status between the indoor and outdoor units,
it may take several minutes for the system to start operating after settings for the
test run are complete.
• After the test run settings are complete, the outdoor units and the connected
indoor units will start operating. Room temperature control will not activate during
test operation (continuous operation).
• If a knocking sound can be heard in the liquid compression of the compressor,
stop the unit immediately and then energize the crank case heater for a sufficient
length of time before restarting the operation.
Test operation setting method (It can be performed in the following two ways)
• Set with test operation setting (refer to installation manual of indoor unit for further
details) available in the remote controller.
• "Cooling Operation" and "Heating Operation" can be set, using "SELECT" button and
"ENTER" button available on the board of display unit.
(*Make sure to perform the first test operation with cooling operation.)
Set as per the procedure given below.
LED display part
Button part
11.2.1. Setting method on outdoor unit board
(1)
Turn on the power of the outdoor unit and enter standby mode.
"POWER/MODE" Lamp lights up.
PUMP
POWER/
DOWN
ERROR
MODE
(L1)
Sign "
": Lights off, "
": Lights on
(2) Press the "ENTER" button for more than 3 seconds.
PUMP
POWER/
DOWN
ERROR
MODE
(L1)
Blink
Sign "
": Lights off, "
": Lights on
(3) Press the "SELECT" button, LED of the test run mode switched between "COOL"
and "HEAT".
Cooling test mode
PUMP
POWER/
DOWN
ERROR
MODE
(L1)
Blink
Sign "
": Lights off, "
": Lights on
Heating test mode
PUMP
POWER/
DOWN
ERROR
MODE
(L1)
Blink
Sign "
": Lights off, "
": Lights on
(4) After confirming the operation mode, Press "ENTER" button.
The display changes as follows, and air conditioner starts operation.
Cooling test mode
PUMP
POWER/
DOWN
ERROR
MODE
(L1)
Blink
Sign "
": Lights off, "
": Lights on
Heating test mode
PUMP
POWER/
DOWN
ERROR
MODE
(L1)
Blink
Sign "
": Lights off, "
": Lights on
(5) Press "ENTER" button.
Air conditioner stopped operation.
PUMP
POWER/
DOWN
ERROR
MODE
(L1)
Sign "
": Lights off, "
": Lights on

11.3. Check list

Check items during test operation.
Is the outdoor unit making any abnormal noise or vibrating significantly?
Is the cold air or hot air blowing from indoor unit according to the operation
mode?
Check that the "ERROR" LED blinks.
If, it has displayed, check the error content as per 12.2. described later.
Operate the unit according to the operating manual provided with the indoor
unit, and check that it is operating normally.
LOW
PEAK
NOISE
CUT
(L2)
(L3)
(L4)
(L5)
LOW
PEAK
NOISE
CUT
(L2)
(L3)
(L4)
(L5)
Blink
LOW
PEAK
NOISE
CUT
(L2)
(L3)
(L4)
(L5)
Blink
LOW
PEAK
NOISE
CUT
(L2)
(L3)
(L4)
(L5)
Blink
LOW
PEAK
NOISE
CUT
(L2)
(L3)
(L4)
(L5)
LOW
PEAK
NOISE
CUT
(L2)
(L3)
(L4)
(L5)
LOW
PEAK
NOISE
CUT
(L2)
(L3)
(L4)
(L5)
(L6)
(L6)
(L6)
(L6)
(L6)
(L6)
(L6)
En-15