Fujitsu AB G36LRTE Series Panduan Desain & Teknis - Halaman 41
Jelajahi secara online atau unduh pdf Panduan Desain & Teknis untuk Pendingin Udara Fujitsu AB G36LRTE Series. Fujitsu AB G36LRTE Series 47 halaman. Ceiling type
Juga untuk Fujitsu AB G36LRTE Series: Panduan Desain & Teknis (47 halaman)
5.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
MODELS :AO G30LETL, AO G36LETL
COOLING
Indoor unit is higher
than outdoor unit
Height
difference H
(m)
Indoor unit is lower
than outdoor unit
HEATING
Indoor unit is higher
than outdoor unit
Height
difference H
(m)
Indoor unit is lower
than outdoor unit
Indoor unit
Connection pipe
1 Indoor unit is higher than outdoor unit.
5
30
-
20
-
1
10
-
7.5
-
5
0.992
0
1.000
-5
1.000
-7.5
-
2
-10
-
-20
-
-30
-
5
30
-
20
-
1
10
-
7.5
-
5
1.000
0
1.000
-5
0.995
-7.5
-
2
-10
-
-20
-
-30
-
Height difference H
H
Outdoor unit
- (02 - 06) -
Pipe length (m)
7.5
10
20
-
-
-
-
-
0.935
-
0.968
0.951
0.982
0.972
0.954
0.986
0.976
0.958
0.994
0.983
0.966
0.994
0.983
0.966
0.994
0.983
0.966
-
0.983
0.966
-
-
0.966
-
-
-
Pipe length (m)
7.5
10
20
-
-
-
-
-
0.954
-
0.990
0.954
0.991
0.990
0.954
0.991
0.990
0.954
0.991
0.990
0.954
0.986
0.986
0.949
0.983
0.983
0.946
-
0.981
0.944
-
-
0.935
-
-
-
Outdoor unit
H
Connection pipe
2 Indoor unit is lower than outdoor unit.
30
40
50
0.908
0.894
0.876
0.923
0.909
0.891
0.938
0.924
0.906
0.942
0.928
0.909
0.946
0.932
0.913
0.954
0.939
0.920
0.954
0.939
0.920
0.954
0.939
0.920
0.954
0.939
0.920
0.954
0.939
0.920
0.954
0.939
0.920
30
40
50
0.931
0.914
0.899
0.931
0.914
0.899
0.931
0.914
0.899
0.931
0.914
0.899
0.931
0.914
0.899
0.931
0.914
0.899
0.926
0.909
0.895
0.924
0.907
0.892
0.921
0.904
0.890
0.912
0.895
0.881
0.903
0.886
0.872
Indoor unit