Fujitsu ABHG45LRTA Panduan Servis - Halaman 16
Jelajahi secara online atau unduh pdf Panduan Servis untuk Pendingin Udara Fujitsu ABHG45LRTA. Fujitsu ABHG45LRTA 30 halaman. Ceiling type
ER R OR D ETEC TION
INDOOR UNIT
and WIRED REMOTE CONTROL
If you use a wireless remote control, the lamp
on the photo detector unit will output error codes
by way of blinking patterns.
If you use a wired type remote control, error
codes will appear on the remote control display.
See the lamp blinking patterns and error codes
in the table. An error display is displayed only
during running.
Indoor unit display
Troubleshooting at the display is possible either
on the wired or wireless remote control.
.
ECONOMY Lamp (green)
TIMER Lamp (orange)
OPERATION Lamp (green)
Remote control
This is possible only on a wired remote control.
If an error occurs, the following display will be shown.
("Er" will appear in the set room temperature display.)
Error code
Unit number of indoor unit
EX. Self-diagnosis
: 0.5s on / 0.5s off
: 0.1s on / 0.1s off
( ) : Number of flashing
2012.07.25
Indoor unit
Wired
OPERATION
TIMER
ECONOMY
remote
lamp
lamp
lamp
control
(green)
(orange)
(green)
Serial communication error
(1)
(1)
Wired remote control communication error
(1)
(2)
Check run unfinished
(5)
(1)
R.C. address or Refrigerant circuit address setting error
(2)
(1)
[Simultaneous Multi]
Indoor unit capacity error
(2)
(2)
Combination error
(2)
(3)
•
(2)
(4)
•
Primary unit, secondary unit set-up error
(2)
(7)
[Simultaneous Multi]
Power supply interruption error
(3)
(1)
Indoor unit PCB model
(3)
(2)
information error
Manual auto switch error
(3)
(5)
Room temp. sensor error
(4)
(1)
Indoor unit Heat Ex. Middle temp. sensor error
(4)
(2)
Indoor unit fan motor error
(5)
(1)
Drain pump error
(5)
(3)
Damper error
(5)
(7)
Indoor unit error
(5)
(15)
Outdoor unit main PCB model information
(6)
(2)
error or communication error
Inverter error
(6)
(3)
Active filter error, PFC circuit error
(6)
(4)
Trip terminal L error
(6)
(5)
Display PCB microcomputers
(6)
(10)
communication error
Description
OPERATION
Connection R.C. address error
(indoor secondary unit) [Simultaneous Multi]
Connection R.C. address error
(indoor unit or branch unit) [Flexible Multi]
15
Indoor unit
Wired
TIMER
ECONOMY
remote
Description
lamp
lamp
lamp
control
(green)
(orange)
(green)
Discharge temp. sensor error
(7)
(1)
Compressor temp. sensor error
(7)
(2)
Outdoor unit Heat Ex. liquid temp. sensor error
(7)
(3)
Outdoor temp. sensor error
(7)
(4)
Suction Gas temp. sensor error
(7)
(5)
•
2-way valve temp. sensor error
(7)
(6)
•
3-way valve temp. sensor error
Heat sink temp. sensor error
(7)
(7)
•
Sub-cool Heat Ex. gas inlet temp. sensor error
(8)
(2)
•
Sub-cool Heat Ex. gas outlet temp.sensor error
Liquid pipe temp. sensor error
(8)
(3)
Current sensor error
(8)
(4)
Discharge pressure sensor error
•
(8)
(6)
Suction pressure sensor error
•
•
High pressure switch error
Trip detection
(9)
(4)
Compressor rotor position detection error
(9)
(5)
(permanent stop)
Outdoor unit fan motor 1 error
(9)
(7)
Outdoor unit fan motor 2 error
(9)
(8)
4-way valve error
(9)
(9)
Coil (expansion valve) error
(9)
(10)
Discharge temp. error
(10)
(1)
Compressor temp. error
(10)
(3)
High pressure error
(10)
(4)
Low pressure error
(10)
(5)
Branch boxes error
(13)
(2)
[Flexible Multi]