Fujitsu ETERNUS DX60 S3 Panduan Perencanaan Lokasi - Halaman 21

Jelajahi secara online atau unduh pdf Panduan Perencanaan Lokasi untuk Penyimpanan Fujitsu ETERNUS DX60 S3. Fujitsu ETERNUS DX60 S3 41 halaman. Hybrid storage systems, all-flash arrays, power synchronized unit
Juga untuk Fujitsu ETERNUS DX60 S3: Konfigurasi Manual Koneksi Server (12 halaman), Panduan Konfigurasi (28 halaman), Panduan Konfigurasi (13 halaman), Tindakan Pencegahan Keselamatan (12 halaman)

Fujitsu ETERNUS DX60 S3 Panduan Perencanaan Lokasi
Chapter 1
ETERNUS DX Installation
1.7

Outlet/Socket Specifications

1.7
Outlet/Socket Specifications
This section explains the power connection specifications of the ETERNUS DX storage systems.
Power Supply Units
Power can be supplied from two power sources in the ETERNUS DX because each enclosure has two power
supply units.
During normal operation, each of the power sources supplies half of the necessary power.
When one of the power supply lines fails, all of the necessary power is supplied from only one power source.
Using the same power supply condition for all of the power supply units is recommended so that different
power supply conditions (such as whether power distribution units are used or not and input voltage) are not
used for the ETERNUS DX.
Current Rating
The following table shows the rating of the current for each power cord that is used for enclosure connec-
tions.

Table 1.3 Rating of the Current for Each Power Cord

Component name
Controller enclosure
Drive enclosure
For power distribution units, make sure that the total rating of the currents for all of the power supply units
that are to be connected does not exceed the normal usage rating of the power distribution unit.
1.7.1

Specifications for Optional Power Supply Products

This section explains the specifications of optional power cords and power related optional products.
For power distribution units, the number of outlets that are required to connect the controller enclosure and
drive enclosures should be taken into consideration, and the most appropriate power distribution units
should then be selected.
When an existing power socket is used, make sure that the plug type of the power distribution unit fits the
existing power socket and that the power supply facility is able to provide sufficient power to the system. If
the plug type does not fit the power socket, electrical work to change the power socket is required. This elec-
trical work must be performed in compliance with the electrical codes of the nation, the municipality, or the
region.
FUJITSU Storage ETERNUS DX60 S3 Disk storage system Site Planning Guide
Copyright 2015 FUJITSU LIMITED
Voltage
AC100V
6.3A
5.3A
21
AC200V
3.0A
2.7A
P3AM-8982-03ENZ0