2N APS MINI ENTRYCOM Panduan Pengguna dan Servis - Halaman 8

Jelajahi secara online atau unduh pdf Panduan Pengguna dan Servis untuk Unit Kontrol 2N APS MINI ENTRYCOM. 2N APS MINI ENTRYCOM 10 halaman.

2N APS MINI ENTRYCOM Panduan Pengguna dan Servis
Setting parameters and access rights using the PC
Main menu of the program contains the following commands:
• Program
Settings ... displays settings dialogue for the communication port of the PC
and code of the service card,
• Start / Stop ... controlling communication with the module,
• Write ... saves the configuration of general properties of the reading module,
• Program
End ... ending the program.
Workspace of the program is divided into 3 parts:
• Area for visualization of the status of the reading module (to be used for verification of
proper connection of the module),
• Area for setting the HW address,
• Area with control elements for setting the general properties of the module.
Indicators are located in the individual parts of the status bar (from the left):
• Indicator of the state of communication with the module (red color indicates error in
communication, flawless communication is indicated by green color),
• Indicator of the process of saving operational parameters,
• Verbal description of the state of communication.
Setting the operational parameters defined in the corresponding input fields is carried out
after communication was established and after the button "Write" was pressed. The setup
program communicates always with one module (module with address specified in the
field "HW Address"). Result of the action is shown by the progress indicator in the second
part of the status bar.
Modules 2N APS mini in the online regime can be controlled via programs APS mini
Administrator, APS mini Events and APS mini ED. These allow, besides programming the
parameters of the modules, also setting access rights and monitoring various events (for
example arriving and leaving persons) and analyze them. The programs can be
downloaded free of charge from the manufacturer's website www.2n.cz.
Setup program APS mini Reader is
designed for operating system Windows
95, Windows NT 4.0 and higher, it does
not require installation. It is designed for
Visualization
of
states
offline regime of readers and it allows
programming operational parameters on
the individual 2N APS mini modules
connected via data bus RS485. It does
not allow programming access rights.
Setting
the
HW address
Connection of modules to the PC
requires either communication converter
RS485/RS232
automatic switching of the direction of
Setting
communication
general
RS485/Ethernet, with settings: 8 data
parameters
bits, even parity, 19 200 bits per second,
1 stop bit.
8
(or
RS485/USB)
or
converter
with