3.5.1

Precleaner Service

Use the following procedure to wash and reoil the
precleaner as indicated in the service schedule. Wash
and reoil the precleaner more often under extremely
dusty or dirty conditions.
1. Place the generator set master switch in the OFF/
RESET position.
2. Disconnect the power to the battery charger.
3. Disconnect the battery, negative (--) lead first.
4. Loosen the cover retaining knob and remove the
cover. Remove the precleaner from the paper
element. Wash the precleaner in warm water with
detergent. Rinse the precleaner thoroughly until all
traces of detergent are eliminated. Squeeze out
excess water (do not wring). Allow the precleaner
to air dry.
5. Saturate the precleaner with new engine oil.
Squeeze out all of the excess oil.
6. Reinstall the precleaner over the paper element.
7. Reinstall the air cleaner cover. Secure the cover
with the cover retaining knob.
8. Reconnect the power to the battery charger.
9. Reconnect the generator set engine starting
battery, negative (--) lead last.
3.5.2

Paper Element Service

Use the following procedure to replace the paper
element at the intervals specified in the service
schedule. Replace the paper element more often under
extremely dusty or dirty conditions.
1. Place the generator set master switch in the OFF/
RESET position.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Loosen the cover retaining knob and remove the
cover.
5. Remove the element cover nut, element cover, and
the paper element with precleaner.
6. Remove the precleaner from the paper element.
Note: Do not wash the paper element or clean it
with pressurized air, as this will damage the
element.
26
Section 3 Scheduled Maintenance, 12 kW Models
7. Replace the element if it is dirty, bent, or damaged.
8. Check the air cleaner base. Make sure it is secure
and not bent or damaged. Also check the element
cover for damage and fit. Replace all damaged air
cleaner components. Remove any loose dirt or
debris from the air cleaner base. Wipe the base
carefully so that no dirt drops into the intake throat.
Check the condition of the rubber seal on the air
cleaner stud and replace the seal if necessary.
9. Reinstall the paper element, precleaner, element
cover, element cover nut, and the air cleaner cover.
Secure the cover with the cover retaining knob.
10. Reconnect the power to the battery charger.
11. Reconnect the generator set engine starting
battery, negative (--) lead last.

3.6 Cooling System

The engine fan draws cooling air through the openings
in the sides and end near the battery. The alternator fan
draws cooling air through openings on the side walls of
the enclosure. The cooling air mixes with the engine
exhaust and is discharged at the exhaust outlet. See
Figure 3-7. To prevent generator set damage caused by
overheating, keep the housing cooling inlets and outlets
clean and unobstructed at all times.
Note: Do not block the generator set cooling air inlets or
mount other equipment above them. Overheating
and severe generator damage may occur.
1
1. Exhaust outlet
2. Alternator air intake (both sides)
3. Engine air intake
Figure 3-7 Cooling Air Intake and Exhaust
2
3
TP-6517 1/11
3
tp6195