2.1 Prestart Checklist

To ensure continued satisfactory operation perform the
following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks require
verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner
element to prevent unfiltered air from entering the
engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer's instructions regarding
battery care and maintenance.
Coolant Level. Check the coolant level according to the
cooling system maintenance information.
Note: Block heater damage. The block heater will fail
if the energized heater element is not immersed
in coolant. Fill the cooling system before turning
on the block heater. Run the engine until it is
warm, and refill the radiator to purge the air from
the system before energizing the block heater.
Drive Belt(s). Check the belt condition of the water
pump and battery charging alternator belt(s).
Exhaust System.
Check for exhaust leaks and
blockages. Check the silencer and piping condition and
check for tight exhaust system connections.
Inspect the exhaust system components for cracks and
corrosion (exhaust manifold, exhaust line, exhaust
clamps, and silencer).
D
Check for corroded or broken metal parts and replace
them as needed.
D
Check for loose, corroded, or missing clamps and
hangers. Tighten or replace the exhaust clamps
and/or hangers as needed.
D
Check that the exhaust outlet is unobstructed.
D
Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components.
Carbon and soot residue indicates an exhaust leak.
Seal leaks as needed.
Carbon Monoxide Detectors. Check the installation
and operation of carbon monoxide (CO) detectors.
TP-6728 10/11

Section 2 Operation

Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.

2.2 Exercising Generator Set

Operate the generator set under load once each week
for 20 minutes.
The operator should perform all of the prestart checks
before starting the exercise procedure.
generator set according to the starting procedure in the
controller section of this manual. While the generator
set is operating, listen for a smooth-running engine and
visually inspect the generator set for fluid or exhaust
leaks.
2.3 Advanced Digital Control
Operation
Figure 2-1 illustrates the user interface on the Advanced
Digital Control (ADC 2100).
Note: Have setup and adjustments of the ADC 2100
performed only by an authorized Kohler
distributor/dealer. The setup and adjustments
are password protected.
1
4
1. LED display
2. Up and down arrow buttons
(use for setup and adjustment only)
3. Generator set master switch
4. Select button (use for setup and adjustment only)
Figure 2-1 ADC 2100 Control
Start the
2
3
GM28707A-C
Section 2 Operation
15