Coyote C25L42LP Instal Manual - Halaman 2
Jelajahi secara online atau unduh pdf Instal Manual untuk panggangan Coyote C25L42LP. Coyote C25L42LP 2 halaman.

C2SL42
NON-COMBUSTIBLE CONSTRUCTION
Insulated Jacket NOT Required
24"
24"
20 1 /2"
OPENING
DEPTH
10 1 /4"
OPENING
HEIGHT
INCLUDING
COUNTERTOP
DOORS / DRAWERS
Combustible material can not be within 24" of the grills frame
This applies to all directions - horizontal & vertical
Shaded area above on "TOP VIEW" illustrates the 24" minimum
requirement (not to scale for rendering purposes)
The grill is designed to hang from the counter top with no support
underneath
Minimum rear clearance for the hood to open is 2"
If you have a wall/partition behind the grill, the minimum rear clearance
to that wall should be at least 7" to allow for ventilation of the exhaust
Regardless if you are using a combustible or non-combustible building material, you must include at least two vents within
the island.
These vents must be at least 20 sq. in. each and allow fresh air to move from the grill cabinet to the exterior environment.
For a propane setup, the vents should be installed lower as propane is heavier than air.
For a natural gas setup, the vents should be located higher in the island, as natural gas is lighter than air.
Do not locate the two vents on the same wall of the island. Cross ventilation is key to allow any excess heat or trapped
gas to dissipate.
Important Note to Installer:
requirements and consumer guidelines. Please refer to your Owners' Manual prior to installing or operating your built-in grill.
1 1 /2"
GRILL
OPENING
TOP VIEW
1 5 /8"
24"
2 1 /2"
G
GAS
1 1 /2"
CONNECTION
GRILL
2 1 /2"
OVERHANG
39 1 /2"
OPENING WIDTH
2 1 /2"
1 1 /2" MIN
G
2"
OPENING
OPENING WIDTH
HEIGHT
FRONT VIEW
This file is not intended to replace your Owners' Manual which contains specific safety
www.coyoteoutdoor.com
INSTALL GUIDE
COMBUSTIBLE CONSTRUCTION
Insulated Jacket Required - Model # CJAKTCS42
11"
OPENING
HEIGHT
INCLUDING
COUNTERTOP
If using combustible material within 24" of the grill frame, you MUST use
the corresponding Coyote Insulated Jacket
Using a insulated jacket, does not waive any other standard installation
procedure (ventilation, connections, etc)
The jacket is designed to hang from the counter top with no support
underneath
Minimum clearance for hood to open is 2"
If you have a wall/partition behind the grill, the minimum rear clearance
to that wall should be at least 7" to allow for ventilation of the exhaust
Ventilation Requirements:
LINER
OPENING
TOP VIEW
4 1 /8"
G
GAS
22 1 /8"
CONNECTION
OPENING
4 1 /8"
DEPTH
42 1 /4"
OPENING WIDTH
4 1 /8"
G
2 3 /4"
DOORS / DRAWERS
OPENING WIDTH
FRONT VIEW
7 /8"
1 3 /4"
7 /8"
JACKET
OVERHANG
1 1 /2" MIN
OPENING
HEIGHT