AB Quality 1769-IQ16F Panduan Petunjuk Instalasi - Halaman 12

Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Unit Kontrol AB Quality 1769-IQ16F. AB Quality 1769-IQ16F 16 halaman. Compact 16-point 24v dc sink/source high-speed input module

12
Compact 16-point 24V dc Sink/Source High-speed Input Module
1769-IQ16F Configuration File
The read/writable configuration data file allows the setup of the digital filter settings
for each of the two input groups. Group 0 is inputs 0 - 7, Group 1 is inputs 8 - 15.
The manipulation of the bits from this file is normally done with programming
software (e.g., RSLogix 500, RSNetworx for DeviceNet, etc.) during initial
configuration of the system. In that case, graphical screens are provided via the
programmer to simplify configuration. However, some systems (e.g., 1769-ADN
DeviceNet Adapter) also allow the bits to be altered as part of the control program
using communication rungs. In that case, it is necessary to understand the bit
arrangement.
15
14
13
0
Filter Time On to Off
Group 1
1
2
3

Spare/Replacement Module Parts

Terminal Block:
Door Label:
Door:
Publication 1769-IN064A-EN-P - April 2003
12
11
10
9
Filter Time Off to On
Group 1
0000000000000000
0000000000000000
0000000000000000
1769-RTBN18 (1 per kit)
1769-RL1 (2 per kit)
1769-RD (2 per kit)
Bit Position
8
7
6
5
Filter Time On to Off
Group 0
Filter Time
2.0 msec
1.0 msec
0.5 msec
0.1 msec
0.0 msec
(1)
Filter Time:
the ON to OFF and OFF to ON hardware delay
times for each input group.
4
3
2
Filter Time Off to On
Group 0
(1)
Bit Setting
0010
0011
0100
0101
0110
Word 0, the Filter Time configures
1
0