Installation

General
Read this entire instruction manual, as well as the
instructions supplied in separate equipment, before
starting the installation. Observe and follow all warnings,
cautions, instructional labels, and tags. Failure to comply
with these instructions could result in an unsafe condition
and/or premature component failure.
These instructions are intended as a general guide only
for use by qualified personnel and do not supersede any
national or local codes in any way. The installation must
comply with all provincial, state, and local codes as well as
the National Electrical Code (U.S.) or Canadian Electrical
Code (Canada). Compliance should be determined prior
to installation.
4AC16LT condensing units use R410A which is an ozone-
friendly HFC refrigerant. The unit must be installed with
a matching indoor coil and line set. 4AC16LT units are
designed for use in expansion valve (TXV) systems only.
A filter drier approved for use with R410A is installed in
the unit.
NOTE: This product has been designed and manufactured
to meet ENERGY STAR criteria for energy efficiency when
matched with appropriate coil components. However,
proper refrigerant charge and proper air flow are critical
to achieve rated capacity and efficiency. Installation of
this product should follow the manufacturer's refrigerant
charging and air flow instructions. Failure to confirm
proper charge and airflow may reduce energy efficiency
and shorten equipment life.
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 shows
torque values for fasteners.
Fastener
Stem Caps
Service Port Caps
Sheet Metal Screws
#8 Machine Screws
#10 Machine Screws
Compressor Bolts
Table 1. Torque Table
Inspection of Shipment
Upon receipt of equipment, carefully inspect it for possible
shipping damage. If damage is found, it should be noted
on the carrier's freight bill. Take special care to examine
the unit inside the carton if the carton is damaged. Any
concealed damage discovered should be reported to the
last carrier immediately, preferably in writing, and should
Page 2 of 20
Torque
8 ft. lbs.
8 ft. lbs.
16 in. lbs.
16 in. lbs.
28 in. lbs.
90 in. lbs.
Issue 1827
include a request for inspection by the carrier's agent. If
any damages are discovered and reported to the carrier
DO NOT INSTALL THE UNIT, as claim may be denied.
Check the unit rating plate to confirm specifications are as
ordered.
Location of Unit
Refer to Figure 1 for installation clearances.
* A service clearance of 30" must be maintained on one of the
sides adjacent to the control box. Clearance to one of the other
three sides must be 36". Clearance to one of the remaining two
sides may be 12" and the final side may be 6".
A clearance of 24" must be maintained between units.
48" clearance required on top of unit. Maximum soffit overhang is
36".
Figure 1. Installation Clearances
Slab Mounting
When installing a unit at grade level, install on slab high
enough above grade so that water from higher ground will
not collect around the unit (Figure 2).
Roof Mounting
Install unit at a minimum of 4" above surface of the roof.
Care must be taken to ensure weight of unit is properly
distributed over roof joists and rafters. Either redwood or
steel supports are recommended.
Figure 2. Slab Mounting
506467-01