Advanced programming
Parameter Name
Default Value
Channel 1 –Switching Channel
Detection Mode
Presence
Lux on level
9
(Switch level on)
Lux off level
9
(Switch level off)
Channel 2 -Dimming Channel
Detection Mode
Presence
Lux on level
9
(Switch level on)
Lux off level
9
(Switch level off)
Light Level
600
(maintained illuminance)
Load Type
DALI
Max Value
100%
Min Value
0%
Memorise
N
On value
99
Off value
0
Burn-in
0
Fade value
10
Fade mins
0
Speed On
40
Speed Set
5
Set Seconds
120
Switch Modes
2 position switch
Default
together
2 position switch
-
separate
1 position switch
-
together
1 position switch
-
separate
10
Range / Options
Description
Presence or
Presence mode allows the output to turn on when movement is detected and off
when movement ceases. Absence mode allows the output to turn off when
Absence
movement ceases, but must be manually turned on first.
1 to 9
Sets a minimum light level below which the Microwave sensor is enabled, allowing
lights to be turned on by movement.
For a higher resolution
a scale of 101-199 is
Note: the Lux Level Off value must always be greater than the Lux Level On value.
available
1 to 9
Sets a maximum light level above which the Microwave sensor is disabled,
preventing lights from being turned on by movement.
For a higher resolution
a scale of 101-199 is
available
Presence or
Presence mode allows the output to turn on when movement is detected and off
when movement ceases. Absence mode allows the output to turn off when
Absence
movement ceases, but must be manually turned on first.
1 to 9
Sets a minimum light level below which the Microwave sensor is enabled, allowing
lights to be turned on by movement.
For a higher resolution
a scale of 101-199 is
Note: the Lux Level Off value must always be greater than the Lux Level On value.
available
1 to 9
Sets a maximum light level above which the Microwave sensor is disabled,
preventing lights from being turned on by movement.
For a higher resolution
a scale of 101-199 is
available
1 to 998 (999
Sets a target light level to be maintained by the lighting system.
disabled)
DSI
Sets the ballast control protocol to DSI.
Sets the ballast control protocol to DALI.
DALI
DALI On
DALI On provides a permanent voltage to DALI ballasts when DALI has not been
implemented correctly in the ballast. Maximum number of ballasts is 5 unless the
relay is disabled then it is 10.
0 to 100%
Maximum dimming output level.
0 to 100%
Minimum dimming output level.
Yes or No
If this is set to Yes, the last manual lux level set will be memorised and used as the
new switch on level.
0 to 99
Dimming output level when switched on (0-99).
0 to 99
Dimming output level when switched off (0-99). If a non-zero off value is set, then
the output will toggle between this value and completely off depending on the
switch level on and off values. For example, if it is light outside, the fittings will be
off if there is no occupancy. If it is dark outside, they will adopt the preset off value.
This feature is only enabled if 'Min value' is set to 99.
0 (disabled) or
Determines how long the output will be at 100% so that lamps 'burn-in'. The 'burn-
in' time is not affected by power supply interruptions.
1 to 999 hours
0 to 99
After occupancy ceases, this dimming output level is loaded for the fade time
(adjustable between 0 and 99).
0 to 99
This is the time period (adjustable between 0 and 99 minutes) that the luminaire
will be held at the fade value before turning off. A value of 0 disables the fade
function.
Measured in 0.1
Determines the dimming response speed after the setup time has finished.
sec intervals.
Measured in 0.1
Determines the dimming response speed during the set up time. Measured in 0.1
sec intervals. If set to 0 will disable dimming for "Set seconds" below, used if
sec intervals.
fittings are required to warm up before dimming.
1 to 999 seconds
Determines how long the dimming response set-up period lasts on power-up or on
setting change. This enables the desired lux level to be achieved rapidly when the
lights come on, or during setup.
-
A single centre biased retractive switch will be used to control both channels
together.
-
A single centre biased retractive switch will be used to control only the dimming
channel.
A single position retractive switch controls both channels together.
-
Two single position retractive switches, controlling the channels separately.
-
UHS5 UNLCDHS