Choosing a Suitable Location
The detector should be sited so that the occupants of the room fall inside the detection pattern shown opposite).
Avoid positioning the unit where direct sunlight may enter the sensor element.
Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
Do not fix the sensor to an unstable or vibrating surface.
Avoid metallic objects directly in front of the sensor head.
MWS6-PRM-VFC connections
MWS6-PRM-VFC-NC (for fail safe operation)
Absence detection
To use absence detection a retractive (momentary) switch must be connected between the 2 terminals on the
diagram. Note that this will be switching mains voltage.
The unit ships with presence detection as default. To change to absence detection, press and release the external
switch 5 times within the first minute of power up. The LED will turn on solid for 30 seconds to indicate absence
mode has been selected.
To change back to presence detection, repeat the above procedure—the LED will flash for 30 seconds to indicate
presence mode has been selected.
Note: the above adjustments can also be made using the UHS5 or UNLCDHS handsets. See Programming sections.
When power is applied to the unit, the load will turn on immediately.
Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off .
Check that the load switches on when movement is detected.
The unit is now ready for programming.
Installation
Power-up test procedure
3