6. INSTALLATION

6.1 CHOOSE THE PLACE OF INSTALLATION
The assembly and especially wiring of the control unit can be
executed only by a trained person with appropriate autho-
rization for the wiring of electric devices, who has suitable
tools and means available. During assembly, it is necessary
to follow all instructions and recommendations listed in this
manual.
TECHNICAL INFORMATION
The regulator must be operated at places corresponding to the
IP cover.
6.2 6.2 ASSEMBLY TO THE OPERATIONAL PO-
SITION
RThe regulator is intended to be installed on a wall in the vertical
position.
The regulator must be installed in such a way that the air can flow
around to prevent overheating.
Comply the minimum recommended standoff distances. The re-
gulator must be installed in such a way that ensures sufficient
access for maintenance, service and disassembling.
The regulator is attached using screws and dowels on a wall or
bolts.
There must not be any flammable materials within a distance of
100 mm from the regulator.
TECHNICAL INFORMATION
After installation of the regulator on the wall, we recommend se-
parating the inner part (electronics+transformer) from the regula-
tion box for easier manipulation.
1.
The regulation must be installed in the way shown in the
above pictures, thus bushings downwards.
2.
2VV. Creating innovative solutions for you and your business since 1995.
Use corresponding screws and dowels for attaching the re-
gulator.
For maintaining the IP cover of the box, use bolts and the
supplied washers.
Driller
4x bolts
4x dowels
4x sealing washers (a part of the delivery)
6.3. ELECTRICAL WIRING AND ELECTRICAL
ASSEMBLY
ATTENTION!
The regulator must be disconnected from the main
electric power supply before any intervention.
The current installation can be executed only by a pro-
fessional with education focused on electric.
The service manual must be monitored together with
the valid state regulations and directives.
The unit must be connected to the main power supply
using isolated, thermally resistant cable which is in ac-
cordance with the diameter and corresponding state
regulations and directives.
All phases of the electric supply to the regulator must
be connected via a protective power circuit breaker of
the corresponding current and type.
The distance between unfastened contacts must be grea-
ter than 3 mm.
The nominal values of electrical parameters of the unit are
listed on the manufacturing label.
The main electric power supply, switched elements and ac-
cessories are connected according to the wiring diagram.
The connected fans must not exceed the nominal current
value of the unit!
Any interventions and changes in inner wiring of the cont-
rol unit are not allowed and lead to a loss of warranty.
In case of fire, it is necessary to extinguish the device using
a powdered or CO2 fire extinguisher.
The unit must be connected in such a way that allows
disconnecting from the source using only one element.
Table of minimum dimensioning of circuit breakers according to
the type of unit.
Recommended circuit breakers:
Circuit breakers
IC-M-AC5-04
IC-M-AC5-07
IC-M-AC5-16
6A
10A
20A
5