3. Setting of In/Output signal
SIGNAL
SW-1
4~20mA
OFF
2-10VDC
OFF
0-10VDC
ON
4. Adjustment of Output signal
Adjust zero or span volume switch to meet the exact value
of output signal in accordance with input signal value.
5. LED Signal Lamp
1) LED
Status
Normal operation
Auto setting
Opening
Closing
2) LED for error
Error
Potentiometer fault
Broken input signal
6. Dead band setting
It is set to adjust the accuracy of the input signal.
0 step : Set as factory default
1 step : 0.1mA
Increase by 0.05mA for each step(2 ~ F step)
If the accuracy is too high, it could cause "HUNTING".
HUNTING means the actuator doesn't stop at the right position
and repeats open or close to find the right position.
HUNTING might be the reason of the motor burning and damages of the potentiometer and PCU card.
CR-TEC
INPUT
SW-2
SW-3
OFF
OFF
ON
OFF
ON
ON
FT(RED)
CL(YEL)
OP(GRE)
ON
ON
ON
ON
ON
LED
LED1 & LED2
LED3 & LED4
Blink every 0.5 sec
LED1 & LED2
Engineering Inc.
OUTPUT
SW-4
SW-5
OFF
ON
OFF
ON
ON
OFF
AT(RED)
ON
Status
ON
ON
[email protected] • www.crtec.com • 203-318-9500