Juga untuk Dell PowerEdge M910: Manual Pembaruan (44 halaman), Manual Pembaruan (21 halaman), Manual Pembaruan (14 halaman), Panduan Instalasi (7 halaman), Manual Pembaruan (28 halaman), Panduan Memulai (12 halaman), Panduan Memulai (12 halaman), Panduan Portofolio (27 halaman), Panduan Teknis (45 halaman), Panduan Memulai (14 halaman), Panduan Memulai (12 halaman), Panduan Teknis (49 halaman)

Dell PowerEdge M910 Panduan Teknis
Dell
5

Power, Thermal, and Acoustic

5.1 Overview

Table 3 lists the environmental specifications for the PowerEdge M910
Temperature
Operating
Storage
Relative Humidity
Operating
Storage
Maximum Vibration
Operating
Storage
Maximum Shock
Operating
Storage
Altitude
Operating
Storage
Altitude
Class G1 or lower as defined by ISA-S71.04-1985 (G1 maximum corrosive contaminant levels
measured at ≤ 50% relative humidity)
PowerEdge M910 Technical Guide
Table 3.
Environmental Specifications
o
o
o
10
to 35
C (50
to 95
10o C per hour
NOTE: For altitudes above 2950 feet, the maximum operating
temperature is derated 1
o
o
o
–40
to 65
C (–40
o
of 20
C per hour
20% to 80% (noncondensing) with a maximum humidity gradation of
10% per hour
5% to 95% (noncondensing) with a maximum humidity gradation of
10% per hour
0.26 Grms at 5–350 Hz in operational orientations
1.54 Grms at 10–250 Hz in all orientations
Half sine shock in all operational orientations of 31 G +/- 5% with a
pulse duration of 2.6 ms +/- 10%
Half sine shock on all six sides of 71 G +/– 5% with a pulse duration
of 2 ms +/– 10%
-15.2m to 3048 m (-50 to 10,000 ft)
Note: For altitudes above 2950 ft, the maximum temperature is
derated 1o F/550 ft
-16 to 10,600 m (-50 to 35,000 ft)
o
F) with a maximum temperature gradation of
o
F/500ft
o
to 149
F) with a maximum temperature gradation
17