Dell PowerVault LTO3-080 Panduan Memulai - Halaman 8

Jelajahi secara online atau unduh pdf Panduan Memulai untuk Penyimpanan Dell PowerVault LTO3-080. Dell PowerVault LTO3-080 10 halaman. Powervault tape systems
Juga untuk Dell PowerVault LTO3-080: Manual (37 halaman), Catatan Rilis (16 halaman), Manual (12 halaman), Manual (24 halaman), Manual (23 halaman), Manual (48 halaman), Buku Pegangan (28 halaman)

Dell PowerVault LTO3-080 Panduan Memulai
Environmental
Temperature (Continuous Operation)
Temperature Ranges (for altitude less than 950 m or
3117 ft)
Humidity Percentage Range
Relative humidity
Storage
Maximum vibration
Operating
Storage
Maximum shock
Operating
Storage
Altitude
Operating
Storage
Operating Altitude De-rating
Particulate Contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and
gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits
specified below and are the reason for the damage and/or failures to your equipment it may be necessary for you
to remediate the environmental conditions that are causing the damage and/or failures. Remediation of
environmental conditions will be the responsibility of the customer.
Air Filtration
8
10 °C to 35 °C (50 °F to 95 °F) with no direct sunlight on
the equipment
NOTE: For information on supported expanded
operating temperature range and configurations,
Owner's Manual support.dell.com/manuals.
see the
10% to 80% Relative Humidity with 26 °C (78.8 °F)
maximum dew point.
5% to 95% RH with 33 °C (91 °F) maximum dew point.
Atmosphere must be non-condensing at all times
0.26 G
at 5 Hz to 350 Hz (all operation orientations).
rms
1.87 G
at 10 Hz to 500 Hz for 15 min (all six sides
rms
tested).
One shock pulse in the positive z axis (one pulse on each
side of the system) of 31 G for 2.6 m in the operational
orientation.
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 m.
3048 m (10,000 ft).
12,000 m ( 39,370 ft).
Up to 35 °C (95 °F) maximum temperature is reduced by 1
°C/300 m (1 °F/547 ft) above 950 m (3,117 ft)
35 °C to 40 °C (95 °F to 104 °F) maximum temperature is
reduced by 1 °C/175 m (1 °F/319 ft) above 950 m (3,117 ft)
40 °C to 45 °C (104 °F to 113 °F) maximum temperature is
reduced by 1 °C/125 m (1 °F/228 ft) above 950 m (3,117 ft)
Data center air filtration as defined by ISO Class 8 per
ISO 14644-1 with a 95% upper confidence limit.