Dell Storage Center SCv2020 Panduan Memulai - Halaman 19
Jelajahi secara online atau unduh pdf Panduan Memulai untuk Penyimpanan Dell Storage Center SCv2020. Dell Storage Center SCv2020 20 halaman. Storage center
Juga untuk Dell Storage Center SCv2020: Panduan Pemilik (42 halaman), Panduan Memulai (19 halaman)
Environmental
Maximum vibration
Operating
Storage
Maximum shock
Operating
Storage
Altitude
Operating
Storage
Airborne Contaminant Level
Class
0.21 G at 5–500 Hz for 15 min
1.04 G at 2–200 Hz for 15 min
Half-sine shock 5 G +/- 5% with a pulse duration of 10 ms +/- 10% (in
operational orientations only)
Half-sine shock 30 G +/- 5% with a pulse duration of 10 ms +/- 10% (all sides)
0 to 3,048 m (0 to 10,000 ft)
For altitudes above 915 m (3,000 ft), the maximum operating temperature is
derated 1°C per 300 m (1°F per 547 ft)
–300 to 12,192 m (–1000 to 40,000 ft)
G1 or lower as defined by ISA-S71.04-1985
19