4.3 Menu "basic settings"
From  press the key P2 to enter the menu "basic settings"
MENU


Enables to set the working time of the automation.

Enables to set the pedestrian opening time (partial opening of the automation).
Enable to activate/ deactivate the water hammer in opening and determine the
duration of the pressure on the mechanic stop.
When the gate is closed the automation executes for short period a closing

movement before starting the opening stage. We suggest to use the water
hammer only if the electric lock is installed.
To activate the electric lock, use the menu .
Enable to activate/ deactivate the water hammer in closing and determine the
duration of the pressure on the mechanic stop.

When the gate reaches the closed position it executes an ' over stroke' equal to the
set time that enables the hook of the electric lock.
We suggest to use the water hammer only if the electric lock is installed.
Impact sensor in opening. The sensor intervenes when an obstacle stops the
stroke of the automation.
The more the values decrease, the more the sensitivity increases ( a lower force

will be necessary to stop the motor).
The more the values increase, the more the sensitivity decreases ( a higher force
will be necessary to stop the motor).
Impact sensor in closing. The sensor intervenes when an obstacle stops the
stroke of the automation.
The more the values decrease, the more the sensitivity increases ( a lower force

will be necessary to stop the motor).
The more the values increase, the more the sensitivity decrease ( a higher force
will be necessary to stop the motor).
Inversion on impact sensor.
OFF: the automation stops the motion in case the impact sensor intervenes.

ON: the automation stops the motion and execute a short inversion in case that the
impact sensor intervenes.
Motor protector
This function enables to limit the current, due to overloads or short circuits, that

goes through the motor in order to avoid any damages.
We suggest to set a value only just higher that the rated current of the motor.
Lack of phases function
The control unit indicates the lack of one or more phases on the power supply.

This option should be activated only if a three-phase power supply is used.
OFF: function lack of phase disabled.
ON: function lack of phase enabled.
Auxiliary function.
It allows to manage the functioning of the R1 optional card.
4 settings are possible:
: output on R1 card is disabled;
: electric lock function is enabled. At every opening movement, before to

power the motor, the R1 output will be enabled for 1,5s. It is NOT necessary to
enable the water hammer.
: "courtesy light function in opening" is enabled. At every opening movement,
after an user command, the R1 output will be enabled for 2s.
: "courtesy light function" is enabled. At every movement (both in opening and
closing), after an user command, the R1 output will be enabled for 2s.
4.4 Menu "special settings" (
From  press the key P2 to enter the menu "special settings"
MENU

Automatic reclosing

The automatic reclosing happens olny with the gate completely opened or furher a
complete pedestrian opening.
6-1622598
REV.3
23/09/2020

(
) :
DESCRIPTION

) :
DESCRIPTION
ITA
ENG
SELECTABLE VALUES
SELECTABLE VALUES
FRA
ESP
DEU
POR
DEFAULT
min-max
5 s — 600s
30 s
5 s — 600s
10 s
0,1 s — 10 s
OFF
0,1 s — 10 s
OFF
1% — 99%
OFF
1% — 99%
OFF
ON — OFF
ON
0,5 A — 14 A
OFF
ON — OFF
OFF
0 — 3
0
DEFAULT
min-max
1 s — 300 s
OFF
MEMO
MEMO