Appliance dimensions
Distance between cooktop and hood (S)
Do not install this exhaust hood over cooktops that burn solid fuel.
Provided a greater clearance is not specified by the manufacturer of the
cooktop, observe the following minimum safety clearances between a cooktop
and the bottom of the hood:
Electric cooktops
Electric barbecues and fryers
Multiburner gas cooktops
< 43,000 BTU (12.6 KW)
and no burner > 15,000 BTU (4.5 KW)
Single burner (Wok) < 20,500 BTU (6 KW)
All other gas cooktops
– If several gas surfaces are installed under the hood, the total output must be
taken into account when determining the minimum safety clearance.
– Be sure to follow the the gas cooktop manufacturer's minimum safety
clearances from easily flammable materials e.g. upper cabinets.
– If local building codes require a greater safety clearance, follow their
specifications.
– If there is more than one appliance beneath the hood and they have different
minimum safety clearances, always select the greater clearance.
See "Important Safety Instructions" for further information.
26
Miele Cooktops
24" (610 mm)
26" (660 mm)
26" (660 mm)
26" (660 mm)
30" (760 mm)
Non-Miele
Cooktops
30" (760 mm)
30" (760 mm)