Introduction
The Plus-X 300 works in conjunction with the Burk Technology ARC Plus transmitter remote
control to provide eight inputs and eight outputs for remote monitoring and control. Metering and
status inputs are sent from the Plus-X 300 to the ARC Plus via Ethernet. The ARC Plus then
reports these values as independent metering and status channels. The relay outputs on the
Plus-X 300 are controlled by the ARC Plus via commands and macros.
The Plus-X 300 has eight (8) inputs, each configurable as metering or status. Eight (8) output
relays allow control of site equipment. Relays may be activated independently or operated in
pairs for mutually-exclusive output.
Compatibility
Before installing the Plus‐ X 300, please verify that the ARC Plus firmware, AutoPilot software
and AutoLoad Plus software versions are current. Updates are available at
www.burk.com/downloads.
The following are minimum software and firmware requirements:
Installation
The Plus-X 300 ships with the following parts, which are required for installation:
(1) Ethernet cable
(1) 15V wall adapter
(1) 2-pin Phoenix-type connector (for power connection)
(1) 9-pin Phoenix-type connector (for input channels)
(2) 12-pin Phoenix-type connectors (for relay outputs)
(4) Rubber feet (for optional horizontal mounting)
For wall mounting, secure the Plus-X 300 using #8 hardware (not included) and chassis cutouts.
Alternatively, the Plus-X 300 may be mounted flat on top of an equipment rack, shelf or another
suitable location.
Input Wiring
Metering and status channels are wired to the Plus-X 300 using the included 9-pin connector
block. To connect metering and status inputs, loosen the screws on the connector block and
connect voltage wiring from the site equipment to the Phoenix connector inputs to align with the
Plus-X 300 Installation and Operation Manual Rev C
Software
ARC Plus firmware
AutoLoad Plus software
AutoPilot® software
Version
2.0 or higher
2.0 or higher
2.6 or higher
1