Miller TM-268 Panduan Teknis - Halaman 23
Jelajahi secara online atau unduh pdf Panduan Teknis untuk Generator Portabel Miller TM-268. Miller TM-268 44 halaman.
8-10. Checking Unit Output After Servicing
Wipe surfaces clean.
Check labels; replace labels that are unreadable or damaged.
Clean battery terminals. Tighten connections.
Clean outside of entire unit.
Belt Driven Generator
Pre-Operational Checks
2
.
Also use output waveforms to
check unit output after servic-
ing (see Section 8-3).
Start generator.
1
Platform AC Receptacles (Not
Shown)
2
Terminal Block TE1
Check open-circuit voltage at plat-
form receptacles. With no load
applied, voltage should be 10%
above receptacle rating.
If output voltage is low or not pres-
ent at platform receptacles, check
voltages at generator terminal
block TE1 (see Section 8-2). If TE1
voltages are correct, check wiring
to platform. If TE1 voltages are in-
correct, repeat troubleshooting pro-
cedures in Section 7-1.
!
Stop unit.
Allow engine to cool, and complete
pre-operational checks in table.
Test Equipment Needed:
803 275
TM-268 819 Page 21